Danfoss VACON NXP Design Manual page 12

Dc/dc converter
Hide thumbs Also See for VACON NXP:
Table of Contents

Advertisement

DC Filters
Design Guide
Drive enclosure size
Drive type
NXP_1640 5
NXP_2060 5
NXP_2300 5
Table 6: DC Filter Selection for Liquid-cooled 690 V Drives According to Energy Storage Requirements
Enclosure size
Drive
CH61
NXP_0170 6
NXP_0208 6
NXP_0261 6
CH62
NXP_0325 6
NXP_0385 6
NXP_0416 6
NXP_0460 6
NXP_0502 6
CH63
NXP_0590 6
NXP_0650 6
NXP_0750 6
CH64
NXP_0820 6
NXP_0920 6
NXP_1030 6
NXP_1180 6
NXP_1300 6
NXP_1500 6
NXP_1700 6
12 | Danfoss A/S © 2023.01
High Voltage @ 750 V DC, f
I
nominal [A]
Filter selection
out
< 1965
< 2469
LDC-1150-6-0-Cxx
< 2756
High Voltage @ 1025 V DC, f
I
nominal [A]
Filter selection
out
< 199
LDC-0160-6-0-Cxx
< 244
< 309
< 385
< 456
< 493
< 545
LDC-0340-6-0-Cxx
< 595
< 699
< 770
< 889
< 972
< 1090
LDC-0700-6-0-Cxx
< 1221
< 1414
< 1558
< 1798
< 2040
= 5 kHz
Low Voltage @ max current, f
s
I
max [A]
out
3280
4120
4200
= 5 kHz
Low Voltage @ max current, f
s
I
max [A]
out
340
416
500
650
770
832
920
975
1180
1300
1500
1640
1840
2060
2360
2600
3000
3400
Selection
= 5 kHz
s
Filter selection
2 x LDC-0700-6-0-Cxx
= 5 kHz
s
Filter selection
LDC-0160-6-0-Cxx
LDC-0340-6-0-Cxx
LDC-0700-6-0-Cxx
LDC-1150-6-0-Cxx
AJ377845348678en-000101 / 172F4785

Advertisement

Table of Contents
loading

Table of Contents