Non-Latched Alarm - ABB REM 543 Technical Reference Manual

Hide thumbs Also See for REM 543:
Table of Contents

Advertisement

ABB Network Partner
4.1.12.1.
Page 46
REM 543 Protection,
Monitoring and Control
Alarm channels are seen as function blocks in the machine terminal configuration:
Alarm channel
Function block
Alarm channel 1
MMIALARM1
Alarm channel 2
MMIALARM2
Alarm channel 3
MMIALARM3
Alarm channel 4
MMIALARM4
Alarm channel 5
MMIALARM5
Alarm channel 6
MMIALARM6
Alarm channel 7
MMIALARM7
Alarm channel 8
MMIALARM8

Non-latched alarm

In a non-latched mode, the ON signal switches between ON and OFF state texts and the
corresponding LED colours. Alarm acknowledgement (ACK) clears the last time stamp
line of the alarm view, but leaves the corresponding alarm LED state unchanged. An
event is generated on the rising and falling edge of the ON signal and by acknowledge-
ment.
Non-latched, steady (example 1)
ACK
ON
ALARM
Off text
On text
Off colour for steady LED
09-24 12:40:00
On colour for steady LED
Non-latched, steady (example 1 continues)
ACK
ON
ALARM
On text
On colour for steady LED
Fig. 4.1.12.1.-1. Example of a non-latched alarm.
Technical Reference Manual
On text
09-24 12:40:00
On colour for steady LED
Off text
09-24 12:40:00
Off colour for steady LED
Off text
09-24 12:40:00
Off colour for steady LED
Part 1, General
On text
On colour for steady LED
alarind4
Off text
Off colour for steady LED
alarind5