57 PREFIX DELAYED ACTION 80 SERIES EXIT DEVICE WIRING DIAGRAM
1. Exit device, 80 Series 57 Prefix Delayed Action
2. Electro-Magnetic lock, 24DC only, 250 MA (1581)
3. Electric hinge (4-wire minimum)
4. Fire alarm, n.c. contact (optional)
- 24VDC
4
- 24VDC
SARGENT Manufacturing Company
100 Sargent Drive
New Haven, CT 06511 USA
800-727-5477
www.sargentlock.com
1-800-727-5477 • www.sargentlock.com
Copyright © 2009, 2022 SARGENT Manufacturing Company. All rights reserved. Reproduction in
whole or in part without the express written permission of SARGENT Manufacturing Company is
prohibited.
4
5
2
5
RESET
( )
6
7
(
)
Notes:
• Wires must be protected from abrasion
• For use with Class 2 circuitry only
• Colors of wires shown are of leads from the exit device, not electric hinge
• Options 4 and 5 must be used in conjunction with each other.
When options are not used, connect TBI-6 and TBI-7 to TBI-8 (Neg.)
• Actuate fire alarm reset switch 5 after power-up to reset alarm
• Check local fire codes for location of reset switch 5
2
1
3
5. Fire alarm reset switch, momentary n.o. contact
(optional 4371)
6. Power supply, 24VDC, 1.8 AMP. regulated (#3510)
7. Keyswitch with time delay, n.c. contact (#4284/4371LT),
for remote momentary access operation (Optional)
ORANGE (-) TBI-3
GREEN (+)
TBI-4
YELLOW
TBI-5
BROWN
TBI-6
BLUE
TBI-7
BLACK
TBI-8
RED
TBI-9
6
7
1
3
A6810G 8/22