NewMar Centurion II Power System Installation & Operation Manual page 23

Dc power system -48 vdc and +24 vdc
Hide thumbs Also See for Centurion II Power System:
Table of Contents

Advertisement

 
 
 
 
 
 
Newmar Rectifiers are compliant with EN6100-4-5, Level 4 without any
Note:
external/upstream surge suppression. To maintain a coordinated approach to surge
suppression, Type 2 SPD should be installed upstream if not fitted in the system.
To ensure correct operation of the SPDs, at least 10m of AC feeder cable is fitted between the
Type 1 and Type 2 protection. If the distance is less than 10m, then loop the cable until at least
10m of cable is used. This ensures correct de-coupling of the SPD devices.
 
 
Notes on AC cable installation and SPDs
The following precautions must be adhered to when installing AC cabling.
 
 
1. Avoid running input and output cables from AC Surge Protection Devices together:
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
2. Avoid "Tee'd" Connections:
 
• Phone: 714-751-0488 • E-mail: techservice@newmarpower.com
Newmar • PO Box 1306, Newport Beach, CA 92663
22

Advertisement

Table of Contents
loading

This manual is also suitable for:

C2rs

Table of Contents