Honeywell NOTIFIER FireWarden-100-2 Instruction Manual page 51

Fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
Zone Assignment
A maximum of five zones can be programmed to each addressable detector. Pressing 1 while
EDIT DETECTOR
viewing Edit Detector Screen #4 displays the following screen:
1=ZONE ASSIGNMENT
00 ** ** ** **
Edit Detector Screen #4
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zone Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Detector Screen #4. Note that the left and right arrow keys can be used to navigate
through the zones and the CLEAR key can be used to quickly clear a zone.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
EDIT DETECTOR
detector currently being programmed. Pressing 1 while viewing Edit Detector Screen #5 will cause
1=NOUN/ADJECTIVE
the following screen to be displayed:
2=DESCRIPTION
*****************
Edit Detector Screen #5
FireWarden 100-2/E — P/N 52778:A 11/04/2005
ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**
Zone Assignment Screen
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
Programming
51