Product Description
EIA-485 (TERM) or EIA-232 (ACS) - TB8
EIA-485 Terminal Mode annunciator connections: Terminal 1 (Out +), 2 (In +),
3 (Out -), 4 (In -)
EIA-232 PC/Printer applications connections: Terminal 1 (Transmit), 2 (Receive),
3 (Ground)
EIA-485 (ACS) - TB9
ACS annunciator connector, Terminal 1 (+) and Terminal 2 (-), requires ferrite bead
1.2.1 Current Availability
The following figure illustrates the maximum current that is possible for each panel circuit and the
total current available from the FACP with optional second transformer.
Refer to the battery calculations section for additional information.
14
Note: If NACs are
configured as two
Style Z (Class A)
circuits, each circuit
can handle 2.5 amps
maximum.
Figure 1.2 Current Availability
6.0 amps with optional second
XRM-24(E) transformer.
3.0 amps max. with only
standard transformer
installed.
FireWarden 100-2/E — P/N 52778:A 11/04/2005
Specifications