Honeywell NOTIFIER FireWarden-100-2 Instruction Manual page 102

Fire alarm control panel
Table of Contents

Advertisement

Programming
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
102
24 Hour Test Time
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be
displayed:
RANGE 0000-2359
Use the 24 Hour Test Time screen to program the time that the DACT will transmit the 24 Hour
Test to the Central Station. A flashing cursor will appear in the lower left corner of the screen.
Enter a four digit number representing the test time using military time (0000 = midnight and 2359
= 11:59PM).
Phone Number
Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following screen to be
displayed:
20 NUMBERS MAXIMUM
The Phone Number screen is used to enter the Central Station phone number that the DACT will be
contacting. A maximum of 20 characters can be entered with valid entries being 0 - 9 and A - F
where A = *, B = #, C = look for secondary dial tone for up to 2 seconds (then dial anyway), D = 3
second pause, E = 5 second pause and F = end of phone number (must be entered at end of phone
number).
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then press
the right arrow key to move the cursor to the right one position. Enter the second digit and repeat
the process until all digits are entered. Press the Enter key to store the phone number in memory.
Enter the digits as you would like the number to be dialed. For example, if it's necessary to dial 9
before dialing a number outside the building, you may wish to pause after dialing 9. Enter 9
followed by D for a three second pause or E for a five second pause then the phone number
followed by an F to indicate the end of the number.
24 HOUR TEST TIME
24 Hour Test Time Screen
PHONE NUMBER
Phone Number Screen
FireWarden 100-2/E — P/N 52778:A 11/04/2005
Master Programming Level

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier firewarden-100-2e

Table of Contents