4.22.15 Print
READ STATUS
1=SERVICE TERMINAL
2=PRINTER/PC
3=PRINT
Read Status Screen #5
DEVICE#
1D001
1D002
1D003
1D004
1D005
1D006
1D007
1D008
1D009
146
To print program data or control panel status, press 3 while viewing Read Status Screen #5. The
following screens will be displayed:
1=HISTORY
2=WALKTEST LOG
3=DETECTOR DATA
1=EXIT PRINTING
Pressing 1 while viewing Print Screen #1 allows the user to print the History file which will detail
all of the system activities since the file was last cleared from memory.
Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which will detail
all of the system activations during walktest since the log was last cleared. Refer to "Walktest" on
page 134 for additional information on the display.
Pressing 3 while viewing Print Screen #1 allows the user to print the detector data for each
addressable smoke detector connected to the system. A printout, similar to the following example,
will be generated if an optional printer is connected to the FACP.
DEVICE TYPE
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
SMOKE (PHOTO)
Chamber Value
The Chamber value should be within the indicated range for the following smoke detectors:
• NP-100(T) and ND-100(R) Addressable Photoelectric Smoke Detectors: 405 - 2100
(obscuration of 1.00%/ft to 3.66%/ft.)
• NI-100 Addressable Ionization Smoke Detectors: 750 - 2100 (obscuration of 0.50%/ft. to
1.44%/ft.)
If the addressable smoke detector's Chamber reading is not within the acceptable range, clean the
detector and check the Chamber value again. If the reading is still not within the acceptable range,
immediately replace the detector.
PRINT
Print Screen #1
PRINT
Print Screen #2
%DRIFT COMP
CHAMBER
20
1281
20
1281
21
1259
20
1309
21
1281
20
1322
20
1280
20
1215
20
1310
FireWarden 100-2/E — P/N 52778:A 11/04/2005
Read Status
TIME/DATE
12:01AM 01-08-2001
12:01AM 01-08-2001
12:01AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001
12:02AM 01-08-2001