Programming
The Communication Format is determined by the type of receiver that the DACT is transmitting to.
Consult your Central Station for proper selection or consult our factory representatives. For any
format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the
appropriate Comm Format screen. The following table describes each format:
Event Codes
Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following screen to be
CENTRAL STATION
displayed:
1=EVENT CODES
Primary/Secondary Screen #4
Pressing the down arrow key allows viewing of all Events associated with the selected
Communication Format. Pressing the number corresponding to the event displayed in each screen
will display its default event code which can be customized by the programmer. For example,
pressing 1 for Pull Station will display the following screen which allows the Event Code to be
changed from the default value.
The tables on the following pages list all of the Events and their default Event Codes for the various
Communication Formats.
104
Table 3.1 Communication Formats
Screen Selection
ADEMCO EXPRESS 4P1
ADEMCO EXPRESS 4P2
3P1S C18 A23
3P1E C18 A23
3P1S C19 A14
3P1E C19 A14
4P1S C18 A23
4P1E C18 A23
4P1S C19 A14
4P1E C19 A14
4P2S C18 A23
4P2E C18 A23
4P2S C19 A14
4P2E C19 A14
ADEMCO CONTACT ID
EVENT CODES
1=PULL STATION
2=MON-USER-DEF-1
3=WATERFLOW
PULL STATION
ALARM
Communication Format Description
4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
Contact ID, DTMF, 1400/2300 ACK
Event Code Screen
Event Code Screen
FireWarden 100-2/E — P/N 52778:A 11/04/2005
Master Programming Level
000