3.4 Installation Precations

When installing multiple SERVOPACKs side by side in a control panel, observe the follow-
ing installation method:
30 mm (1.2in.) or more
Front Panel
Install SERVOPACK perpendicular to the wall so that the front panel (digital operator
mounted face) faces outward.
Cooling
Provide sufficient space around each SERVOPACK to allow cooling by fan and natural con-
vection.
Where mounted side by side
When installing SERVOPACKs side by side, provide at least 10mm (0.4in.) space between
them and at least 50mm (2in.) space above and below them as shown in the figure above.
Install cooling fans above the SERVOPACKs to prevent the temperature around each SER-
VOPACK from increasing excessively and also to maintain the temperature inside the con-
trol panel evenly.
Environments in Control Panel
Maintain the following conditions inside the control panel:
• Ambient temperature for SERVOPACK: 0 to 55°C
• Humidity: 90%RH or less
• Vibration: 4.9 m/s
• Condensation and freezing: None
• Ambient temperature to ensure long-term reliability: 45°C or less
• Altitude of 1000 m max.
FAN
10 mm (0.4in.) or more
2
E-16
FAN
5.0 mm (2in.) or more
5.0 mm (2in.) or more