Auxiliary Output - Wiring

1
3
16
Raymote
Scheduling AUX
Outputs Control
2
OMRON LY2F 24AC
1.
P9 Auxiliary is a dry contact output: It requires external
power supply to energize connected devices.
2.
Load on P9 must not exceed 3 Amps. If the load is
larger than 3 Amps, use P9 auxiliary output to drive a
field-installed contactor. For pumps, blowers, and other
applications rated above 3 Amps, use field-supplied
relay (Raypak kit# 008784F).
3.
Use the Normally Closed (NC) and Normally Open (NC)
terminals to drive a 3-way valve. This configuration
typically uses an external 24VAC supply.