Blower "Pre-Purge"
for 45 sec
Spark
Is Water Setpoint,
NO
Temperature and
"Heating" displayed?
YES
Unit Heating until
demand is satisfied.
Was Water
NO
Temperature
reached?
YES
Blower "Post-Purge"
for 3 minutes
Wait for new Heat
demand
END
Check for damaged or loose wires and terminals.
Diff Sw Closed
Check Blower and Air Pressure switch:
- Replace Pressure switch if failing open or close.
Diff Sw Open
- Replace Blower if operation is intermittent.
Fan Lockout
Ing Try Failure
Check Gas valve, Gas supply and spark igniter:
- Check gas supply and valve operation.
Ign 60 min Delay
- Check Igniter and wire. Replace if damaged.
Ignition Lockout
Check for damaged or loose wires and terminals.
Clock/Fireman Sw
Switch connected to safety loop is in OFF mode.
Water Sw Open
Verify water flow / pressure. Clean Filter/Strainer.
Vent Sw Open
Vent switch open. Troubleshoot extractor if installed.
Hi Limit 1 Fault
Temperature Limit switch open. Verify water flow.
Hi Limit 2 Fault
Inspect internal thermostat (Unitherm Governor) and
Cabinet Temp Lm
bypass valve.
Air SW Open
Air Pressure Switch failed in operation. Verify Blower
Diff Sw Fault
operation. Check for air inlet/outlet obstructions. Verify
Fan Lockout
air pressure.
Flame Lost
Verify gas supply. Verify gas valve operation.
Flame Flickering
Cut power, verify and clean igniter rods.
Flue Over Temp
Verify obstructions. Troubleshoot extractor if installed.
Outlet Over Temp
Verify water flow. Verify gas supply and combustion.
Low Flow Fault
Verify water flow. Verify Pump operation. Adjust Flow
High Flow Fault
as necessary. Verify filter pressure and clean if needed.
Control Logic - Flow Chart