Do you have a question about the CROSSWIND Series and is the answer not in the manual?
Questions and answers
Genny Davidson
April 29, 2025
We have a Crosswind 50i, where does the wire come from or go to after we remove the jumper on the bottom of Terminal #5 & #6??
The directions read, Install the automation control wires for Heat to terminal #5 & #6, where are the automation control wires located??
1 comments:
Mr. Anderson
May 15, 2025
The automation control wires for heat connect to terminals #5 and #6 on a Raypak Crosswind 50i after removing the jumper.
This answer is automatically generated
Michael Georges
May 1, 2025
Does the heat pump require a dedicated power supply to the heat pump or can it run off the same power supply as the pump as long as it has enough amps
1 comments:
Mr. Anderson
May 16, 2025
The Raypak Series heat pump requires a dedicated 60 Amp breaker, so it must have its own dedicated power supply and cannot share the same power supply as the pump.
This answer is automatically generated
Curtis Winkowski
March 17, 2025
How do i set the manual defrost interval on a model 50-I
1 comments:
Mr. Anderson
March 17, 2025
To set the manual defrost interval on a Raypak CROSSWIND Series model 50-I, follow these steps:
1. Ensure the heater is in heating mode. 2. Press and hold the FAN and MINUS buttons together for 5 seconds to start manual defrosting. 3. The HEATING indicator will flash continuously during defrosting. 4. After defrosting, the HEATING indicator will stop flashing.
Important Notes: - Manual defrosting intervals should be at least 30 minutes apart. - The compressor should run for at least 10 minutes before performing another manual defrost.
This answer is automatically generated
Kelly
January 17, 2025
Why can't I get my crosswind to heat over 90
1 comments:
Mr. Anderson
May 14, 2025
The Raypak Series Crosswind heater may not reach temperatures over 90 degrees if it does not have a HEAT command, in which case the unit will remain in OFF mode. This prevents it from heating beyond the default or limited setting.
Page 1
INSTALLATION AND OPERATION MANUAL Crosswind Side Discharge Heat Pump Pool Heater Inverter Models CROSSWIND-30-I through -65-I On/Off Models CROSSWIND-40-O through -65-O (Canada Only) FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
Page 2
With all of the above information in hand, please contact us and ask to register your brand new heat pump or do it online at: http://warranty.raypak.com (800)-260-2758 M-F 8:30 - 4:30 EST You will be given a Warranty Registration Confirmation...
CONTENTS 1. WARNINGS ............. 4 6. CONTROLS ............17 Pay Attention to These Terms ......... 4 Inverter Models Only ..........17 General Precautions ..........5 On/Off Models Only ..........18 Using the On/Off Display Unit ....... 18 2. WATER CHEMISTRY ..........5 7.
1. WARNINGS Pay Attention to These Terms Indicates the presence of immediate hazards which will cause severe personal injury, death or DANGER substantial property damage if ignored. Indicates the presence of hazards or unsafe practices which could cause severe personal injury, WARNING death or substantial property damage if ignored.
Make sure power is turned off before opening the case and General Precautions performing service work. 1. The heater must be installed by a qualified electrician. Attention 2. Set heating temperature within the recommended 1. Follow the instructions to set a comfortable water range to maximize comfort.
Chlorinators must feed downstream of the heater and Automatic Chlorinators have an anti-siphoning device to prevent chemical backup and Chemical Feeders into the heater when the pump is shut off. All chemicals must be introduced and completely diluted See plumbing diagrams starting with Figure 10. into the pool or spa water before being circulated through the heater.
3. Do not stack anything that will block air flow near the WARNING: Do not install the unit within 3 ft (0.9 m) inlet or outlet areas, or have any barrier within 20 in of fossil-fuel-burning heaters. Air intake along the sides (508 mm) behind the main heater, or the efficiency of of this heater could disturb the combustion process of the heater will be reduced.
Page 8
Figure 3. Hurricane Tie Down Instructions...
Page 9
On/Off Model - Component Locations, Figure 7. On/Off Model - Component Locations, Front View Right Side View Inverter Models 60Hz (Heating and Cooling) Models Unit Size (BTUH) Raypak P/N Rheem P/N RUUD P/N Jacuzzi P/N CROSSWIND-30-I 17738 17742 17746 17750...
1. Shutoff diverter valves, preferably three-way valves Water Connections which allows for a bypass route, on the inlet and outlet lines of the heater are required: CAUTION: The heater inlet and outlet connections are NOT interchangeable. They must be connected as a.
4. ELECTRICAL WIRING Breaker Size Min. (Amp) Models Power Circuit Wiring Ampacity min. max. Electrical installation should be done by a licensed CROSSWIND-30-I electrician only. CROSSWIND-40-I 1. Confirm the power supply is at the rated voltage of the appliance and make the connection. 17.2A CROSSWIND-50-I 208-230VAC...
6. CONTROLS Screen Lock If no button is used within 30 seconds, the screen will lock Inverter Models Only automatically. At this point the backlight will turn off and 0% The Display controls general operation. The layout, main will display. functions and buttons are shown below.
On/Off Models Only Heat/Cool Mode The Display controls general operation. The layout, main 1. Press the MODE button to switch from one mode to functions and buttons are shown below. another. NOTE: Available only in heat and cool models. Setting pool water temperature Temperature can be adjusted either when the machine is on or off.
If your heater has been installed correctly, operating the Setting the OFF time heater is an easy task. The display allows you to turn the heater ON or OFF and adjust the temperature settings for 1. Press CLOCK to access the timer function. the pool or spa.
4. Cover the heater when not in use to protect it from Model Identification the weather. The model number of the heater can be found on the name 5. Clean the heater exterior with standard household plate, Figure 1. detergent or clean water. Never use gasoline, paint thinner or other flammable liquids.
8. TROUBLESHOOTING No. Display Failure Description If these solutions, below, do not work, contact your dealer. High gas pressure protection Do not attempt to repair the heater yourself. Low gas pressure protection Failure Reason Solution No water flow protection Wait for the power to be Main power off 3-phase sequence (only for 3-phase heaters) restored...
Page 26
Limited Warranty does NOT cover any shipping costs to and from Raypak’s designated service provider or to or from the installation site. All of the foregoing costs and expenses are your responsibility, unless applicable state law provides otherwise.
Page 27
ANY persons or agencies other than those authorized by Raypak. Raypak reserves the right at all times to inspect, or require the return of, the defective Heater or component part and to verify warranty coverage at its factory. Warranty service CANNOT be initiated until the status of the warranty coverage has been established.
Page 28
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 1-800-260-2758 Fax (805) 278-5468 Litho in U.S.A.
Need help?
Do you have a question about the CROSSWIND Series and is the answer not in the manual?
Questions and answers
We have a Crosswind 50i, where does the wire come from or go to after we remove the jumper on the bottom of Terminal #5 & #6?? The directions read, Install the automation control wires for Heat to terminal #5 & #6, where are the automation control wires located??
The automation control wires for heat connect to terminals #5 and #6 on a Raypak Crosswind 50i after removing the jumper.
This answer is automatically generated
Does the heat pump require a dedicated power supply to the heat pump or can it run off the same power supply as the pump as long as it has enough amps
The Raypak Series heat pump requires a dedicated 60 Amp breaker, so it must have its own dedicated power supply and cannot share the same power supply as the pump.
This answer is automatically generated
How do i set the manual defrost interval on a model 50-I
To set the manual defrost interval on a Raypak CROSSWIND Series model 50-I, follow these steps:
1. Ensure the heater is in heating mode.
2. Press and hold the FAN and MINUS buttons together for 5 seconds to start manual defrosting.
3. The HEATING indicator will flash continuously during defrosting.
4. After defrosting, the HEATING indicator will stop flashing.
Important Notes:
- Manual defrosting intervals should be at least 30 minutes apart.
- The compressor should run for at least 10 minutes before performing another manual defrost.
This answer is automatically generated
Why can't I get my crosswind to heat over 90
The Raypak Series Crosswind heater may not reach temperatures over 90 degrees if it does not have a HEAT command, in which case the unit will remain in OFF mode. This prevents it from heating beyond the default or limited setting.
This answer is automatically generated