100 • vacon
18
Unbalance
(Warning only)
22
EEPROM
checksum fault
24
Counter fault
25
Microprocessor
watchdog fault
26
Start-up
prevented
29
Thermistor
fault
31
IGBT
temperature
(hardware)
32
Fan cooling
34
CAN bus
communication
35
Application
37
Device changed
(same type)
38
Device added
(same type)
39
Device removed
40
Device
unknown
41
IGBT temperature
42
Brake resistor
overtemperature
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Unbalance between power modules in
paralleled units.
Subcode in T.14:
S1 = Current unbalance
S2 = DC-Voltage unbalance
Parameter save fault
faulty operation
component failure
Values displayed on counters are
incorrect
faulty operation
component failure
Start-up of the drive has been
prevented.
The thermistor input of option board has
detected too high a motor temperature
IGBT Inverter Bridge overtemperature
protection has detected too high a short
term overload current
Cooling fan of the frequency converter
does not start, when ON command is
given
Sent message not acknowledged.
Problem in application software
Option board or power unit changed.
New device of same type and rating.
Option board added.
Option board removed.
Unknown option board or drive.
Subcode in T.14:
S1 = Unknown device
S2 = Power1 not same type as Power2
S3 = NXS or NXP1 and star coupler
S4 = Software and ctrl unit incompatible
S5 = Old control board version
IGBT Inverter Bridge overtemperature
protection has detected too high a short
term overload current
FAULT TRACING
Should the fault re-occur, contact your
local distributor.
Should the fault re-occur, contact your
local distributor.
Have a critical attitude towards values
shown on counters.
Reset the fault and restart.
Should the fault re-occur, contact your
local distributor.
Cancel prevention of start-up if this can
be done safely.
Check motor cooling and loading
Check thermistor connection
(If thermistor input of the option board is
not in use it has to be short circuited)
Check loading.
Check motor size.
Contact your local distributor.
Ensure that there is another device on
the bus with the same configuration.
Contact your distributor. If you are
application programmer check the
application program.
Reset. Device is ready for use.
Old parameter settings will be used.
Reset. Device is ready for use.
Old board settings will be used.
Reset. Device no longer available.
Contact the distributor near to you.
Check loading.
Check motor size.