Download Print this page

Unitronics Vision V130-T2 User Manual page 7

Advertisement

Vision™PLC+HMI
Veuillez noter qu'il est recommandé de sauvegarder toutes les données conservées dans la RAM, afin
d'éviter de perdre des données lors du changement de la batterie lorsque l'alimentation est coupée. Les
informations sur la date et l'heure devront également être réinitialisées après la procédure
Wiring
▪ Do not touch live wires.
▪ Install an external circuit breaker. Guard against short-circuiting in external wiring.
▪ Use appropriate circuit protection devices.
▪ Unused pins should not be connected. Ignoring this directive may damage the device.
▪ Double-check all wiring before turning on the power supply.
▪ To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
▪ Do not use tin, solder, or any substance on stripped wire that might cause the wire
Caution
strand to break.
▪ Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure
Use crimp terminals for Use crimp terminals for wiring;
- Controllers offering a terminal block with pitch of 5mm: 26-12 AWG wire (0.13 mm
- Controllers offering a terminal block with pitch of 3.81mm: 26-16 AWG wire (0.13 mm
1. Strip the wire to a length of 7±0.5mm (0.270–0.300").
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Input or output cables should not be run through the same multi-core cable or share
the same wire.
Allow for voltage drop and noise interference with I/O lines used over an extended distance.
Use wire that is properly sized for the load.
The controller and I/O signals must be connected to the same 0V signal.
I/Os
V130/V350/V130J/V350J/V430J-T2 models comprise a total of 12 inputs and 12 transistor outputs.
Input functionality can be adapted as follows:
12 inputs may be used as digital inputs. They may be wired in a group via a single jumper
as either npn or pnp.
According to jumper settings and appropriate wiring:
- Inputs 10 and 11 can function as either digital or analog inputs.
- Inputs 0, 2 and 4 can function as high-speed counters, as part of a shaft-encoder,
or as normal digital inputs.
- Inputs 1, 3 and 5 can function as either counter reset, as part of a shaft-encoder,
or as normal digital inputs.
-
If inputs 0, 2 and 4 are set as high-speed counters (without reset), inputs 1, 3 and 5 can function
as normal digital inputs.
Unitronics
–3.31 mm
2
2
).
– 1.31 mm
2
2
).
7