Vision™PLC+HMI
* Note that for models V130/V350, the bezel width is up to 8.4 mm (0.33").
Model
V130V130J
V350/V350J
V430J
Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
1. Make a panel cut-out of the appropriate size:
2. Slide the controller into the cut-out, ensuring that the rubber seal is in place.
3. Push the mounting brackets into their slots on the sides of the panel as shown in the figure below.
4. Tighten the bracket's screws against the panel. Hold the bracket securely against the unit while
tightening the screw.
5. When properly mounted, the controller is squarely situated in the panel cut-out as shown in the
accompanying figures.
Unitronics
Dimensions: V430J
Cut-out
92x92 mm (3.622"x3.622")
92x92 mm (3.622"x3.622")
122.5x91.5 mm (4.82"x3.6")
V130/V350/V130J/V350J
View area
58x30.5mm (2.28"x1.2")
72x54.5mm (2.95"x2.14")
96.4x55.2mm (3.79"x2.17")