Unitronics Vision V130-J-B1 User Manual

Unitronics Vision V130-J-B1 User Manual

Plc+hm
Hide thumbs Also See for Vision V130-J-B1:

Advertisement

Quick Links

Vision™PLC+HMI
V130-33-B1/V130-J-B1
V350-35-B1/V350-J-B1
V430-J-B1
General Description
The products listed above are micro-PLC+HMIs, rugged programmable logic controllers that comprise
built-in operating panels.
Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications,
and additional documentation are located in the Technical Library in the Unitronics website:
https://unitronicsplc.com/support-technical-library/
Item
Screen
Keypad
Function Keys
Com Port, Built-in
RS232/485
USB device,
mini-B
Com Ports, separate
The user may install a CANbus port (V100-17-CAN), and one of the following:
order, user-installed
* V430J/V350/V350J comprises both RS232/485 and USB ports; note that only one channel may be used at a time.
Standard Kit Contents
Item
Controller
Terminal Blocks
Battery (installed)
Slides
(2 sets of key labels)
Mounting Brackets
Rubber Seal
Unitronics
V130-B1
V130J-B1
2.4"
Yes
None
Yes
Yes
None
None
RS232/RS485 port (V100-17-RS4/V100-17-RS4X)
Ethernet (V100-17-ET2)
Profibus Slave (V100-17-PB1)
V130-B1
V130J-B1
None
Yes (2 parts)
User Guide
V350-B1
V350J-B1
3.5" Color Touch
Yes*
Yes*
V350-B1
V350J-B1
Yes
Yes
Yes
Yes
Yes
V430J-B1
4.3" Color Touch
None
Yes
Yes*
Yes*
Yes*
Yes*
V430J-B1
None
Yes (4 parts)
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Vision V130-J-B1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Unitronics Vision V130-J-B1

  • Page 1 The products listed above are micro-PLC+HMIs, rugged programmable logic controllers that comprise built-in operating panels. Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications, and additional documentation are located in the Technical Library in the Unitronics website: https://unitronicsplc.com/support-technical-library/ V130-B1...
  • Page 2: Alert Symbols And General Restrictions

    ▪ All examples and diagrams are intended to aid understanding, and do not guarantee operation. Unitronics accepts no responsibility for actual use of this product based on these examples. ▪ Please dispose of this product according to local and national standards and regulations.
  • Page 3: Panel Mounting

    4. Tighten the bracket’s screws against the panel. Hold the bracket securely against the unit while tightening the screw. 5. When properly mounted, the controller is squarely situated in the panel cut-out as shown in the accompanying figures. V130/V350/V130J/V350J Unitronics...
  • Page 4 DIN-rail as shown in the figure to the right. UL Compliance The following section is relevant to Unitronics’ products that are listed with the UL. The following models: V130-33-R34, V130-J-R34, V130-T4-ZK1, V350-35-RA22, V350-J-RA22, V350-35-R34, V350-J-R34, V430-J-R34 are UL listed for Hazardous Locations.
  • Page 5 Class I, Division 2, Groups A, B, C and D These Release Notes relate to all Unitronics products that bear the UL symbols used to mark products that have been approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.
  • Page 6 à risques, Class I, Division 2, Groups A, B, C et D. Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été certifiés pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.
  • Page 7: Wiring Procedure

    ▪ Allow for voltage drop and noise interference with I/O lines used over an extended distance. Use wire that is properly sized for the load. ▪ The controller and I/O signals must be connected to the same 0V signal. Unitronics...
  • Page 8: Power Supply

    To maximize system performance, avoid electromagnetic interference by: ▪ Mounting the controller on a metal panel. ▪ Connect each common and ground connection directly to the earth ground of your system. ▪ For ground wiring uses the shortest and thickest possible wire. Unitronics...
  • Page 9 To do so, remove the RS485 connector (pins 1 & 6) from the PLC and connect a standard RS232 programming cable. Note that this is possible only if DTR and DSR signals of RS232 are not used (which is the standard case). Unitronics...
  • Page 10 ** Causes the unit to function as an end unit in an RS485 network USB Port ▪ The USB port is not isolated. Caution Make sure that the PC and the controller are grounded to same potential. The USB port may be used for programming, OS download, and PC access. Unitronics...
  • Page 11: Opening The Controller

    Do not force the board into place; doing so may damage the controller. 2. Replace the back cover of the controller and fasten the corner screws. Note that you must replace the back cover securely before powering up the controller. Unitronics...
  • Page 12: Technical Specifications

    PLC with Flat panel, Color touch display 3.5’’ V350-J-B1 V430-J-B1 PLC with Flat panel, Color touch display 4.3’’ You can find additional information, such as wiring diagrams, in the product’s installation guide located in the Technical Library at www.unitronics.com. Power Supply V130-B1 V350-B1 V430J-B1...
  • Page 13 120K dynamic data (recipe parameters, datalogs, etc.) 192K fixed data (read-only data, ingredient names, etc) Expandable via SD card. See Removable Memory below HMI displays Up to 1024 Program scan time 20µs per 1kb 15µs per 1kb of typical of typical application application Unitronics...
  • Page 14: Removable Memory

    Compatible with standard SD and SDHC; up to 32GB store datalogs, Alarms, Trends, Data Tables, backup Ladder, HMI, and OS. See Note 2 Notes: 2. User must format via Unitronics SD tools utility. Communication Ports Port 1 1 channel, RS232/RS485 and USB device (V430/V350/V350J only). See Note 3...
  • Page 15 8.4Hz to 150Hz, 1G acceleration. The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market.