17.1.2 Refrigerant piping insulation

17.2 Connecting the refrigerant piping

17.2.1 About connecting the refrigerant piping

FXHA-A
VRV system air conditioner
4P673749-1A – 2022.11
Outer diameter (Ø)
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
15.9 mm (5/8")
(a)
Depending on the applicable legislation and the maximum working pressure of the unit
(see "PS High" on the unit name plate), larger piping thickness might be required.
Use polyethylene foam as insulation material:
-
with a heat transfer rate between 0.041 and 0.052  W/mK (0.035 and
0.045 kcal/mh°C)
-
with a heat resistance of at least 120°C
Insulation thickness
Pipe outer diameter (Ø
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
15.9 mm (5/8")
Ø
Ø
i
i
Ø
Ø
p
p
t
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the
thickness of the insulation materials should be at least 20  mm to prevent
condensation on the surface of the insulation.
Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
Connecting the refrigerant piping to the indoor unit
Connecting the refrigerant piping to the outdoor unit
Insulating the refrigerant piping
Keeping in mind the guidelines for:
-
Pipe bending
-
Flaring pipe ends
-
Using the stop valves
Temper grade
Annealed (O)
) Insulation inner diameter
p
)
i
8~10 mm
12~15 mm
14~16 mm
17~20 mm
17
Piping installation
|
(a)
Thickness (t)
≥0.8 mm
Insulation thickness (t)
≥10 mm
≥13 mm
≥13 mm
≥13 mm
Installer and user reference guide
Ø
t
61