Download Print this page

Advertisement

Quick Links

KTM
a
Fire Damper – round
https:
//
www.smay.eu
Installation manual

Advertisement

loading
Need help?

Need help?

Do you have a question about the KTM and is the answer not in the manual?

Questions and answers

Summary of Contents for SMAY KTM

  • Page 1 Installation manual Fire Damper – round https: www.smay.eu...
  • Page 2: Table Of Contents

    INSTALLATION TECHNOLOGY – WALL AND CEILING STRUCTURESS OF GREAT THICKNESS ...................... 9 INSTALLATION TECHNOLOGY – MONTAGE AWAY FROM RIGID WALL (SILICATE BOARDS) ......................9 CONNECTION DIAGRAM OF LIMIT SWITCHES IN THE KTM DAMPER ....... 10 Version 6.00 Page 1 of 10 Date of editing: 15.09.2022 r.
  • Page 3: Installation Technology

    Do not pull by baffle to open or close fire damper, it may cause permanent damage, not covered by the warranty. During KTM damper test, with size DN>125, while opening baffle, fold back the bumper (as shown on the fig. 5) so as to unlock the bolt caught on it, allowing free rotation of the baffle.
  • Page 4: Installation Technology - Ceiling

    After the mortar has dried (about 48 hours), remove the supports or suspension, check the fire damper correct operation and leave it in open position (installing in KTM damper thermal fuse as shown on the fig. 6). Figure 2. Thermal fuse installation method Figure 3.
  • Page 5: Installation Technology - Rigid Wall

    After the mortar has dried (about 48 hours), remove the supports or suspensions, check the fire damper correct operation and leave it in open position (installing in KTM damper thermal fuse as shown on the fig. 6). Figure 5. Installation of KTM fire dampers in rigid wall with 115 mm thickness Version 6.00...
  • Page 6 Installation manual Figure 6. Installation of KTM fire dampers in rigid wall with horizontal rotation axis of baffle Figure 7. Installation of KTM fire dampers in rigid wall with vertical rotation axis of baffle Version 6.00 Page 5 of 10...
  • Page 7: Installation Technology - Flexible Wall

    After mounting the collar, remove the supports or suspension, check the fire damper correct operation and leave it in open position (installing in KTM damper thermal fuse as shown on the fig. 12). Installation method of fire dampers KTM in flexible wall with 75 mm thickness Figure 8.
  • Page 8 Installation manual Figure 9. Installation method of fire dampers KTM in flexible wall with 100 mm thickness Figure 10. Installation method of fire dampers KTM in flexible wall with horizontal rotation axis of baffle Version 6.00 Page 7 of 10...
  • Page 9 Installation manual Figure 11. Installation method of fire dampers KTM in flexible wall with vertical rotation axis of baffle Figure 12. Installation method of fire dampers KTM in flexible wall with 125 mm thickness Version 6.00 Page 8 of 10...
  • Page 10: Installation Technology - Wall And Ceiling Structuress Of Great Thickness

    Whereas in case of walls and ceilings with thickness higher than 150 mm: the KTM fire dampers are mounted in such a way, that the damper installation limit i.e.
  • Page 11: Connection Diagram Of Limit Switches In The Ktm Damper

    CONNECTION DIAGRAM OF LIMIT SWITCHES IN THE KTM DAMPER Microswitches D2SW-3L2M ( OMRON ) are used in KTM fire dampers as limit switches to signal the baffle position. By the microswitch it is possible to connect two circuits, normally closed and normally open (closing only at the moment of contact with baffle), Figure 15.