Version 1.6 SMAY reserves the right to make changes to this document Table of Contents INSTALLATION TECHNOLOGY – CEILING ....................3 INSTALLATION TECHNOLOGY – RIGID WALL .................... 5 INSTALLATION TECHNOLOGY – STANDARD WALL ................... 7 INSTALLATION TECHNOLOGY – STRUCTURES THICKER THAN 140 MM ............ 9...
4. After the mortar has dried (about 48 hours), remove the supports or suspenions, check the fire damper correct operation and leave it in open position. Fig.1. Installation method of fire dampers KWP-L in ceiling Version: 1.6 Page 3 of 12...
Page 4
Installation Manual – Fire damper KWP-L Fig.2. Mounting method of fire dampers KWP-L in ceiling Fig.3.Proposed dimensions of mounting brackets for installation in a ceiling 140 mm thick Version: 1.6 Page 4 of 12 Date: 25.11.19...
4. After the mortar has dried (about 48 hours), remove the supports or suspensions, check the fire damper correct operation and leave it in open position. Fig.4. Installation method of fire dampers KWP-L in rigid wall with vertical rotation axis of damper blade Version: 1.6...
Page 6
Installation Manual – Fire damper KWP-L Fig.5. Installation method of fire dampers KWP-L in rigid wall with horizontal rotation axis of damper blade Fig.6. Mounting method of fire dampers KWP-L in rigid wall Version: 1.6 Page 6 of 12 Date: 25.11.19...
7. After mounting the flange, remove the supports or suspenions, check the fire damper correct operation and leave it in open position. FIg.7. Installation method of fire dampers KWP-L in standard wall with vertical rotation axis of damper blade Version: 1.6 Page 7 of 12 Date: 25.11.19...
Page 8
Installation Manual – Fire damper KWP-L Fig.8. Installation method of fire dampers KWP-L in standard wall with horizontal rotation axis of damper blade Fig. 9. Mounting method of fire dampers KWP-L in standard wall 75 mm thick Version: 1.6 Page 8 of 12...
Installation Manual – Fire damper KWP-L Fig.10. Mounting method of fire dampers KWP-L in standard wall 100 mm thick 4. Installation technology – Structures thicker than 140 mm Fig.11. Mounting method of fire dampers KWP-L in structures thicker than 140 mm Version: 1.6...
Installation Manual – Fire damper KWP-L In rigid, standard walls and ceilings with a thickness less than or equal 140 mm, fire dampers KWP-L should be mounted in this way that an axis of the fire damper blade matches the axis of the structure.
Page 11
Installation Manual – Fire damper KWP-L Fig. 12. Montage of fire dampers KWP-L away from wall construction according to 2. (silicate boards) Fig. 13. Montage of fire dampers KWP-L away from wall construction. (silicate boards) Version: 1.6 Page 11 of 12...
Page 12
Installation Manual – Fire damper KWP-L Fig. 14. Montage of fire dampers KWP-L away from wall construction. (silicate boards) Version: 1.6 Page 12 of 12 Date: 25.11.19...