Ginlong solis S6 Series User Manual page 21

Hybrid inverter
Table of Contents

Advertisement

4. Installation
4.7.3 BMS Port Connection
Take out the pre-made CAN cable from the package and connect one end to battery CAN
port and then connect another end to the inverter BMS port. Cable Length: 3 meters.
NOTE:
Before connecting CAN cable with the battery, please check whether the
communication pin sequence of the inverter and the battery match;
If it does not match, you need to cut off the RJ45 connector at one end of the
CAN cable and adjust the pin sequence according to the pin definitions of
both inverter and battery.
Pin definition of the inverter CAN Port is following
EIA/TIA 568B.
CAN-H on Pin 4: Blue
CAN-L on Pin 5: Blue/White
4.7.4 Meter Port Connection
Take out the pre-made Meter cable from the package and connect RJ45 end to inverter
Meter port and then connect another end with loose RS485 A & B pins to the meter RS485
terminal. Cable Length: 5 meters.
NOTE:
Pin definition of the Meter Port is following
EIA/TIA 568B.
RS485A on Pin
RS485B on Pin
NOTE:
Compatible Smart Meter Pin definition.
Eastron SDM630MCT – Pin 13 is RS485B & Pin 14 is RS485A.
Eastron SDM630 – Pin B is RS485B & Pin A is RS485A.
A
B
1:
Orange/white
2:
Orange
CAN
Figure 4.22
METER
Figure 4.23
20
User Manual
RJ45terminal
1 2 3 4 5 6 7 8
CAN-L
CAN-H
RJ45terminal
1 2 3 4 5 6 7 8
RS485B
RS485A