7.12.2
The units are designed for operation only with non-flammable liquids to
DIN EN 61010-2-010.
Overtemperature alarm
S A F E
7.12.3 Overtemperature and low level protection testing
Every 6 month or before the unit is running unattended for longer periods this protection should be
tested.
Overtemperature alarm
S A F E
32
Overtemperature and low level protection
The overtemperature cut-off point is activated close above 110 °C
and can not be changed.
If the bath temperature rises above the overtemperature cut-off
point or the liquid level is too low ( 6.2):
1. Alarm sounds as dual-tone signal.
SAFE
2.
3. The red LED
Heater switches off on all poles;
Pump and refrigerating unit are switched off electronically.
Rectify cause of fault.
Wait until the bath temperature has cooled below the cut-off point.
Unlock the thermostat ( 7.12.4).
Therefore:
Remove the heat transfer liquid of the thermostat ( 6.2).
Turn on thermostat and set the set temperature to a value a couple
degrees above ambient temperature.
The heater of the thermostat will now start heating. Attention the
heater will get very hot. Don't touch it at any time.
Wait about 45 seconds until the protection device will shut off the
heater and the pump and the alarm
If it takes more then 45 seconds for the overtemperature protection
to get triggered immediately cut out the power manually and have
the equipment checked by the LAUDA Service Constant Tempera-
ture Equipment or the local service organization.
Refill the heat transfer liquid ( 6.2).
Unlock (reset) the alarm ( 7.12.4).
Shut off the control head and turn it on again. The alarm must have
disappeared now.
for overtemperature cut-off point appears in the display.
above the fault triangle
Starting up
Alpha
flashes.
SAFE
will appear.
June 20, 2018/ YACE0092