21
|
Configuration
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
: Default
Installer and user reference guide
72
If you want to use...
Unit sensor only (or remote sensor (if installed))
Unit sensor (or remote sensor (if installed)) AND
remote controller sensor
(a)
If setting 10(20)-6-01 + 10(20)-2-01 or 10(20)-2-02 or 10(20)-2-03 are set at the same
time, then setting for group connection: 10(20)-6-01 has priority.
(b)
If setting 10(20)-6-02 + 10(20)-2-01 or 10(20)-2-02 or 10(20)-2-03 are set at the same
time, then setting 10(20)-2-01 or 10(20)-2-02 or 10(20)-2-03 have priority.
(c)
When the remote controller sensor is used in group control, set 10(20)-6-02 and
10(20)-2-03.
Setting: Thermostat differential changeover (if remote sensor is used)
If the system contains a remote sensor, set the increase/decrease increments.
If you want to change increments to...
1°C
0.5°C
Setting: Automatic changeover differential
Set the temperature difference between the cooling setpoint and the heating
setpoint in automatic mode (availability depends on the system type). The
differential is the cooling setpoint minus the heating setpoint.
If you want to set...
0°C
1°C
2°C
3°C
4°C
5°C
6°C
7°C
Setting: Auto-restart after power failure
Depending on the needs of the user, you may disable/enable the automatic restart
after a power failure.
If you want auto-restart after power failure...
Disabled
Enabled
(a)
(b)(c)
(1)
Then
M
SW
12 (22)
4
(1)
Then
M
SW
10 (20)
6
(1)
Then
M
SW
12 (22)
2
Example
01
cooling 24°C/heating 24°C
02
cooling 24°C/heating 23°C
03
cooling 24°C/heating 22°C
04
cooling 24°C/heating 21°C
05
cooling 24°C/heating 20°C
06
cooling 24°C/heating 19°C
07
cooling 24°C/heating 18°C
08
cooling 24°C/heating 17°C
(1)
Then
M
SW
12 (22)
5
VRV system air conditioner
4P715928-1 – 2022.11
01
02
01
02
01
02
FXHQ-A