NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will NOT occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
In places with weak reception, keep distances of 3  m or more to avoid
electromagnetic interference of other equipment and use conduit tubes for power
and transmission lines.
Take care that in the event of a water leak, water cannot cause any damage to
the installation space and surroundings.
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone and the location is selected according the
applicable legislation.
Drainage. Make sure condensation water can be evacuated properly.
Paper pattern for installation (accessory). Use the paper pattern when selecting
the installation location. It contains the dimensions of the unit and the locations
of suspension bolts, piping outlet, drain piping outlet and electric wiring inlet.
Ceiling insulation. When conditions in the ceiling exceed 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, then additional
insulation is required (minimum 10 mm thickness, polyethylene foam).
Spacing. Mind the following requirements:
Minimum distance to the wall: 30  mm left and right of the unit, however,
≥200 mm is recommended for easier servicing.
≥30
Minimum and maximum distance to the floor:
-
Minimum: 2.5 m to avoid accidental touching.
-
Maximum: Depends on the capacity class. See
a
c
d
a Discharge
b Suction
c Obstacle
d Floor
b
(mm)
16
Unit installation
|
≥30
(mm)
4
"21.1 Field
setting" [
 70].