FXHQ-A
VRV system air conditioner
4P715928-1 – 2022.11
(mm)
(mm)
A
FXHQ32 960
FXHQ63 1270
FXHQ100 1590
A Unit dimension
B Suspension bolt pitch
a Rear left drain piping outlet hole
b Rear wiring outlet location
c Wall hole for rear piping outlet (⌀100 mm)
d Top panel wiring outlet position
e Discharge
f1 Nut (field supply)
f2 Double nut (field supply)
h Hanger bracket
g Washer for hanger bracket (accessory)
i Suspension bolt
j Top panel drain piping connection position
k Top panel gas side piping connection position
l Top panel liquid side piping connection positions
Level. Use the level to make sure the unit is installed horizontally. If possible,
install the unit so the drain piping side is slightly tilted (maximum 1°)
A Drain piping tilted to the right, or to the right and back
B Drain piping tilted to the left, or to the left and back
Front view
G
H
J
a
b
Top (ceiling) view
A
B
C
D
E
F
e
B
C
D
920
378
324
1230
533
479
1550
693
639
A
A
B
B
A/B
16
Unit installation
|
c
j
k
l
d
f1
g
g
h
f2
i
E
F
G
H
270
375
398
377
425
530
553
532
585
690
713
692
Installer and user reference guide
J
260
415
575
47