Displays, alarms and messages
7.3 Diagnostic messages
Diagnostics message
Frequency too high
Undertemperature
Discrepancy error
Internal discrepancy error
Input shorted to P
Auxiliary voltage too high
Auxiliary voltage too low
64
Error
Meaning
code
311
The maximum switching frequency of
H
the F-module has been exceeded.
312
The minimum permissible temperature
H
limit has been violated.
314
The 1oo2 discrepancy time set for op‐
H
eration has been exceeded.
Possible causes:
Incorrect parameter assignment
Wire break of the supply cable of the
sensor
315
An error occurred during the plausibility
H
check of the input signal between the
processors. You must correct the error
within 100 hours.
Possible causes:
The input signal is disturbed, For ex‐
ample, by impermissibly high elec‐
tromagnetic interference.
A high-frequency input signal is
present. for example, due to mutual
interference of sensors or because
the signal is above the sampling fre‐
quency of the input signal.
There is a brief interruption / transi‐
ent short-circuit of the sensor line
(loose contact).
The sensor/switch bounces.
31C
Possible causes:
H
The input signal is short-circuited
with P.
There is a short-circuit in the inter‐
nal sensor supply with P.
There is a short circuit of two sensor
supplies.
The capacitance of the connected
sensor for the configured test time is
too high.
The sensor is defective.
321
The supply voltage is too high.
H
322
The supply voltage is too low.
H
Remedy
Reduce the switching frequency of the
sensor.
Operate the F-module in the specified
temperature range. (See section "Tech‐
nical specifications (Page 67)")
Check the discrepancy time, the sensors
and their wiring.
Use shielded cables to reduce influ‐
ences on EMC
Reduce the input frequency
Check the wiring of the sensor.
Check the wiring.
Check the configured test time and
the process wiring.
Replace the sensor.
Check the supply voltage.
Check the supply voltage.
Equipment Manual, 08/2021, A5E45647528-AD