Displays, alarms and messages

7.3 Diagnostic messages

7.3
Diagnostic messages
Overview
The F-module generates a diagnostic interrupt for each diagnostics message described in the
following table. In addition, the DIAG LED on the I/O module flashes red or the MT LED lights up
yellow.
In addition, channel-specific diagnostics are indicated by the corresponding channel fault/status
LEDs.
The diagnostics messages can be read from the diagnostics buffer of the CPU, for example.
Module faults are indicated as diagnostics (module status).
After fault correction, you must reintegrate the F-module in the safety program.
You can find additional information on passivation and reintegration of F-I/O in the
programming and operating manual "SIMATIC Industrial Software S7 F/FH Systems -
Configuring and Programming
109773062)".
Table 7-8
Diagnostics messages of F-DI 16×24VDC HA
Diagnostics message
Overtemperature
Wire break
Parameter error
No supply voltage
Communication error
60
(https://support.industry.siemens.com/cs/ww/en/view/
Error
Meaning
code
5
An excessively high temperature was
H
measured in the F-module.
6
Possible causes:
H
The cable between the module and
the sensor is broken. The channel is
not wired (open).
There is a short-circuit between
channels with different signals.
See the note below
message.
10
Parameter assignment errors include:
H
The F-module cannot use the pa‐
rameters (unknown, invalid combi‐
nation, etc.).
The F-module parameters have not
been configured.
11
Supply voltage missing or too low
H
13
A communication error has occurred.
H
The possible causes depend on the
module type used.
Remedy
Operate the F-module in the specified
temperature range. (See section "Tech‐
nical specifications (Page 67)")
Once the fault has been eliminated, the
F-module must be removed and inser‐
ted or the power switched OFF and ON
Establish a cable connection.
Disable wire break detection for the
channel in the configuration.
Eliminate the short-circuit.
regarding this
*1)
Correct the parameter assignment.
Check the supply voltage P on the
terminal block
Check the terminal block type
The solution depends on the cause.
You can find information on this in the
manual for the F-module.
Equipment Manual, 08/2021, A5E45647528-AD