Siemens SIMATIC ET 200SP HA Equipment Manual page 21

Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Parameter
Pulse stretching (s)
Flutter monitoring
Number of signal changes
Monitoring window (s)
Sensor supply
Short-circuit test
Time for short-circuit test (ms)
Startup time of sensor after
short-circuit test (ms)
Module parameters
Diagnostics missing supply volt‐
age L+
Behavior after channel fault
Channel n, n+8 (channel pair)
Sensor evaluation
Sensor supply for 1oo2
Discrepancy behavior
Discrepancy time (ms)
Reintegration after discrepancy
error
Channel n
F-DI 16x24VDC HA
Equipment Manual, 08/2021, A5E45647528-AD
Value range
None
0.05 s
0.1 s
0.5 s
1 s
2 s
Enabled
Disabled
2 to 31
0.5 to 100 s
(If 0 s is set, the monitoring window
is 0.5 s long.)
Internal
External
Enabled
Disabled
(not available in the redundant con‐
figuration)
1 ms to 2 s (in 17 steps)
0.5 ms to 2 s (in 18 steps)
Enabled (display only)
Passivate the entire module
Passivate channel
1oo1 evaluation
1oo2 evaluation, equivalent
1oo2 evaluation, non-equivalent
Each sensor has its own sensor
supply
Both sensors on one sensor sup‐
ply
Supply value 0
Supply last valid value
10 ms to 30 s
Test 0-Signal not necessary
Test 0-Signal necessary
Parameters/address space
Default value
Parameter
reassign‐
ment in RUN
None
No
Disabled
No
5
No
2 s
No
Internal
No
Enabled
No
10 ms
No
10 ms
No
Enabled
No
Passivate channel
No
1oo1 evaluation
No
Each sensor has its
No
own sensor supply
Supply last valid val‐
No
ue
30 ms
No
Test 0-Signal not
No
necessary
5.1 Parameters
Scope
All channels
All channels
All channels
All channels
All channels
All channels
All channels
All channels
Module
Module
Channel pair
Channel pair
Channel pair
Channel pair
Channel pair
21