Diagnostics message
Discrepancy error, channel sta‐
tus 0/0
Discrepancy error, channel sta‐
tus 0/1
Discrepancy error, channel sta‐
tus 1/0
Discrepancy error, channel sta‐
tus 1/1
Overload or internal sensor sup‐
ply short-circuit to ground
F-address memory not accessi‐
ble
No valid F-address available
Sensor signal flutters
F-DI 16x24VDC HA
Equipment Manual, 08/2021, A5E45647528-AD
Error
Meaning
code
300
Possible causes:
H
The process signal is faulty.
301
The sensor is defective.
H
The configured discrepancy time is
302
H
too low.
There is a short-circuit between the
303
H
cable of an "unconnected sensor"
and the sensor supply cable.
Wire break in the line of a "connec‐
ted sensor" or the sensor supply ca‐
ble
An error occurred during the dis‐
crepancy check.
307
Possible causes:
H
The internal sensor supply is short-
circuited to ground.
Impermissibly high electromagnet‐
ic interference is present.
See the note below
message.
30D
No valid PROFIsafe address is stored in
H
the retentivity memory.
Possible causes:
Initial commissioning
Deliberate parameter change of the
PROFIsafe address
Deviation between set and actual
configuration of the plant
30E
F_source_address and F_destina‐
H
tion_address parameters invalid
310
Too many signal changes have occurred
H
within the time configured with the
"Monitoring window" parameter.
The "Monitoring window" setting is
too high.
The "Number of signal changes" pa‐
rameter setting is too low.
A momentary interruption/short cir‐
cuit of the sensor cable (loose con‐
tact) is present.
Impermissibly high electromagnet‐
ic interference is present.
The sensor/switch bounces.
The sensor is defective.
Remedy
Check the process signal.
Replace the sensor.
Check the parameter assignment of
the discrepancy time.
Check the process wiring.
Eliminate the overload.
Eliminate the short circuit in the
process wiring.
Check the "Sensor supply" parame‐
ter.
regarding this
*1)
Eliminate/reduce the electromag‐
netic interference.
Assign the PROFIsafe address during
initial commissioning or when delib‐
erately changing parameters.
Check the consistency between the
nominal and actual configuration.
Check F_source_address and F_destina‐
tion_address parameters
Check the "Monitoring window" pa‐
rameter.
Check the "Number of signal
changes" parameter.
Check the process wiring.
Eliminate/reduce the electromag‐
netic interference.
Replace the sensor.
Displays, alarms and messages
7.3 Diagnostic messages
63