Diagnostics message
Discrepancy error, channel sta‐
tus 0/0
Discrepancy error, channel sta‐
tus 0/1
Discrepancy error, channel sta‐
tus 1/0
Discrepancy error, channel sta‐
tus 1/1
Overload or internal sensor sup‐
ply short-circuit to ground
F-address memory not accessi‐
ble
No valid F-address available
Sensor signal flutters
F-DI 16x24VDC HA
Equipment Manual, 08/2021, A5E45647528-AD
Error
Meaning
code
300
Possible causes:
H
•
The process signal is faulty.
301
•
The sensor is defective.
H
•
The configured discrepancy time is
302
H
too low.
•
There is a short-circuit between the
303
H
cable of an "unconnected sensor"
and the sensor supply cable.
•
Wire break in the line of a "connec‐
ted sensor" or the sensor supply ca‐
ble
•
An error occurred during the dis‐
crepancy check.
307
Possible causes:
H
•
The internal sensor supply is short-
circuited to ground.
•
Impermissibly high electromagnet‐
ic interference is present.
See the note below
message.
30D
No valid PROFIsafe address is stored in
H
the retentivity memory.
Possible causes:
•
Initial commissioning
•
Deliberate parameter change of the
PROFIsafe address
•
Deviation between set and actual
configuration of the plant
30E
F_source_address and F_destina‐
H
tion_address parameters invalid
310
Too many signal changes have occurred
H
within the time configured with the
"Monitoring window" parameter.
•
The "Monitoring window" setting is
too high.
•
The "Number of signal changes" pa‐
rameter setting is too low.
•
A momentary interruption/short cir‐
cuit of the sensor cable (loose con‐
tact) is present.
•
Impermissibly high electromagnet‐
ic interference is present.
•
The sensor/switch bounces.
•
The sensor is defective.
Remedy
•
Check the process signal.
•
Replace the sensor.
•
Check the parameter assignment of
the discrepancy time.
•
Check the process wiring.
•
Eliminate the overload.
•
Eliminate the short circuit in the
process wiring.
•
Check the "Sensor supply" parame‐
ter.
regarding this
*1)
•
Eliminate/reduce the electromag‐
netic interference.
•
Assign the PROFIsafe address during
initial commissioning or when delib‐
erately changing parameters.
•
Check the consistency between the
nominal and actual configuration.
Check F_source_address and F_destina‐
tion_address parameters
•
Check the "Monitoring window" pa‐
rameter.
•
Check the "Number of signal
changes" parameter.
•
Check the process wiring.
•
Eliminate/reduce the electromag‐
netic interference.
•
Replace the sensor.
Displays, alarms and messages
7.3 Diagnostic messages