Sub-Zero ICB700 T Series Troubleshooting Manual page 9

Table of Contents

Advertisement

Troubleshooting Guides
PROBLEM
(Continued)
H. Warm Freezer Temperatures
without "SERVICE" Flashing
Pointers:
1. "Sr" appears during Diagnostic
Mode, see:
• Unit in Showroom Mode
2. Evap Temp -29°C (-20°F) or
lower, see:
• Door ajar
• Lights ON w/door closed
• Evaporator fan fault
• Compartment thermistor mis-
read
• Evaporator heavily frosted
• Sealed system fault: leak or
partial restriction
3. Evap Temp between -28°C
(-19°F) and -17°C (0°F), see:
• Warm food load
• High room ambient
• Door ajar
• Condenser Air Flow
• Compartment thermistor mis-
read
• Sealed system fault: leak
4. Evaporator Temp -17°C (0°F)
or higher, see:
• Power to compressor fault
• Sealed system Fault: leak,
restriction, inefficient compres-
sor
NOTE:
"Pointers" do not apply to
cabinet initial pulldown from
ambient temperatures.
NOTE:
To clear non-flashing
SERVICE indicator after repairs,
press ALARM key for 15 sec-
onds.
7005836 - Revision A - January, 2009
International Integrated
International Integrated
POSSIBLE CAUSE
Evaporator Fan Fault
a. Top hinge cover missing, not depress-
ing fan switch
b. Fan blade obstructed or out of position
c. Faulty fan switch
(NOTE: A compressor must be running)
d. Evaporator. fan motor disconnected
e. Evaporator fan motor defective
(NOTE:
Compressor must be running)
Compartment Thermistor Misread
Evaporator Heavily Frosted
a. Door or drawer ajar
b. Evaporator fan fault
c. Compartment thermistor misread
d. Defrost heater disconnected or faulty
e. Defrost terminator disconnected or
faulty.
f. Defrost sense line disconnected.
g. No power from control board to defrost
circuit
Power to Compressor Fault
NOTE:
For ICB700TF/I, see Error Code
Troubleshooting Guide
Sealed System Fault
Sealed System Leak
Sealed System Restriction
Inefficient Compressor
8-10
Series
Series
(ICB700 T
all)
(ICB700 T
all)
TEST / ACTION
a. Replace hinge cover.
b. Move obstruction or reposition blade.
c. Check for 230 V AC to fan switch, depress
fan switch and check for 230 V AC from fan
switch. Replace switch if defective. (NOTE:
there are two fan switches in the drawer
area)
d. Check electrical connections of motor.
Reconnect / repair bad connections.
e. Check for 230 V AC at fan motor with fan
switch depressed. Replace motor if defec-
tive.
Check resistance of freezer compartment
thermistor for 30,000 to 33,000 ohms at 0°C
(32°F). Replace if defective.
a. See Door or Drawer Ajar on previous page.
b. See Evaporator Fan Fault above.
c. See Compartment Thermistor Misread
above.
d. Check electrical connections. Reconnect /
repair bad connections. Check resistance of
heater, 30-38 Ohms, replace if defective.
e. Check electrical connections, Reconnect /
repair bad connections or replace terminator
if defective.
f. Manually initiate defrost by pressing ICE key
for 10 seconds. If defrost lasts exactly 5
minutes, check all connections of gray/white
wire from terminator to J4-4 on control
board. Reconnect / repair bad connections.
g. Manually initiate defrost by pressing ICE key
for 10 seconds. Check for 230 V AC at E2
on control board. Replace control board if
defective.
Check for 230 V AC at E7 on control board.
Replace control board if defective.
See Sealed System Troubleshooting Guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Icb700tc/iIcb736tc/iIcb700trIcb736trIcb700tf/i

Table of Contents