Samson 3349 Mounting And Operating Instructions page 59

Aseptic angle valve with usp-vi diaphragm, valve with pneumatic actuator and positioner, valve combined with pneumatic piston actuator and positioner
Table of Contents

Advertisement

18. For micro-flow valve version: secure
plug (2) with threaded pin (6.1) (see
Fig. 9-4).
19. Check the concentricity of the plug (see
section 9.7).
20. Clean the flange area that will be locat-
ed above the diaphragm with detergent
and a brush. Rinse it with water and ap-
ply a non-damaging mild sanitizer.
21. Push the plug (2) together with plug stem
(3) and diaphragm (24) into the stan-
dard yoke (20).
22. Place the standard yoke (20) together
with the plug stem (3), plug (2) and dia-
phragm (24) onto the body (1).
23. Apply a suitable lubricant to the bolts
(34).
24. Tighten the screws (34) on the standard
yoke (20) gradually in a crisscross pat-
tern until the valve bonnet touches the
body flange.
Note
Greater deformation forces are required for
new diaphragms (in comparison to already
installed diaphragms). We recommend
shaping the new diaphragms beforehand us-
ing conventional hex screws:
− Tighten the conventional hex screws as de-
scribed in step 24.
− Replace the conventional hex screws with
the existing screws (34).
− Tighten the screws (34) as described in
step 24.
EB 8048-2 EN
25. Mount actuator. See associated actuator
documentation and the 'Installation' sec-
tion.
26. Adjust lower or upper signal bench
range. See associated actuator docu-
mentation.
Fig. 9-3: X shape of washers
Fig. 9-4: Threaded pin on the plug stem/plug
Servicing
3
6.2
6.2
2
3
6.1
24
2
9-7