Example For Mintime/Maxtime Logic - netvox R313CB User Manual

Wireless window sensor with glass break detector
Table of Contents

Advertisement

SetLastMessage
contactswitch
ResendtimeRsp
devicetype
GetLastMessage
ResendtimeReq
GetLastMessage
ResendtimeRsp
Resendtime = 0x00 or 0xFF, No additional data will be sent
Resendtime = 0x03 to 0xFE, The device will send data after triggering, and then supplement the last status data after 3-254s.
When the device is triggered quickly, additional data can be sent
Resendtime=0, When the reed switch is closed immediately after magnetic opening, it will only receive reed switch status =1
Resendtime=3, Close the reed switch as soon as it is opened, and you will receive reed switch status =1, it will be received after 3
seconds reed switch status =0
(3) Configure the device to resend data within 5s after sending the packet
Downlink: 1FFF050000000000000000
Device return:
9FFF000000000000000000 (configuration success)
9FFF010000000000000000 (configuration failure)
(4) Read R313CB device parameter
Downlink: 1EFF000000000000000000
Device return:
9EFF050000000000000000 (device current parameter)

5.3 Example for MinTime/MaxTime logic

Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime
Sleeping(MinTime)
Wakes up and collects data
REPORTS 2.8V
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BtteryVoltageChange
value.
0x9F
Status (0x00_success)
0x1E
(1Byte, Unit:1s, range:3-254s),
0x9E
when 0 or 255 no resend,
Sleeping(MinTime)
Wakes up and collects data
REPORTS 2.8V
Reserved (9Bytes, Fixed 0x00)
Resendtime
default is no resend
MaxTime
Wake up and collects data
REPORTS 2.8V
8
Reserved (8Bytes,Fixed 0x00)
Reserved (8Bytes,Fixed 0x00)