Data Report; Example Of Reportdatacmd - netvox R718PA1 User Manual

Wireless co sensor
Hide thumbs Also See for R718PA1:
Table of Contents

Advertisement

5. Data Report

The device will send a version package report immediately after power-on. Then, it will send a report
data with the concentration of carbon monoxide after it is powered on for 20s.
The device sends data according to the default configuration before any other configuring.
Default setting:
MaxTime: Max Interval = 3min = 180s
MinTime: The MinTime configuration is not available.
*But the software has restriction, MinTime must be configured a number greater than 0.
Note: 1. The cycle of the device sending the data report is according to the default.
2. R718PA1 reports the concentration of carbon monoxide.
Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver
http://www.netvox.com.cn:8888/cmddoc

5.1 Example of ReportDataCmd

FPort: 0x06
Bytes
Version
Version– 1 byte –0x01——the Version of NetvoxLoRaWAN Application Command Version
DeviceType– 1 byte – Device Type of Device
ReportType – 1 byte –the presentation of the NetvoxPayLoadData, according the devicetype
NetvoxPayLoadData– Fixed bytes (Fixed =8bytes)
Tips
1. Battery Voltage:
If the battery is equal to 0x00, it means that the device is powered by a DC power supply.
2. Version Packet:
When Report Type=0x00 is the version packet, such as 0157000B04202309250000, the firmware
version is 2023.09.25.
3. Data Packet:
When Report Type=0x01 is data packet.
to resolve uplink data.
1
1
ReportType
1
ReportType
5
Var (Fix=8 Bytes)
NetvoxPayLoadData