Configuration Information; Level Offset Description - Magnetrol ECLIPSE 700GWR Installation And Operating Manual

Hart guided wave radar level transmitter
Table of Contents

Advertisement

20 mA
20 mA
60 cm
60"
4 mA
24 cm
4 mA
24"
10 cm
10"
Example 1
20 mA
20 mA
60 cm
60"
4 mA
4 mA
24 cm
10 cm
24"
10"
Example 2
BE 57-660 Eclipse Model 700 Guided Wave Radar Transmitter
3.4

Configuration Information

This section is intended to offer additional configuration-
related details with respect to some of the parameters
shown in the Menu in Section 2.6.5.

3.4.1 Level Offset Description

The parameter referred to as Level Offset in the ECLIPSE
Model 700 DEVICE SETUP/BASIC CONFIG menu is
defined as the desired level reading when liquid surface is
at the tip of the probe.
The ECLIPSE Model 700 transmitter is shipped from the
factory with Level Offset set to 0. With this configuration,
all measurements are referenced from the bottom of the
probe. See Example 1.
Level Units = inches
Example 1 (Level Offset = 0 as shipped from factory):
Level Units = Centimeters
Probe Model = 7zT
Probe Model = 7YT
Probe Mount = NPT
Probe Mount = NPT
Probe Length = 72 in
Probe Length = 90 cm
Level Offset = 0 in
Level Offset = 0 cm
Dielectric Range =
Dielectric Range = Above 10
Above 10
In those applications in which it is desired to reference all
4 mA = 24 in
4 mA = 24 cm
measurements from the bottom of the vessel, the value of
20 mA = 60 in
Level Offset should be changed to the distance between the
20 mA = 60 cm
bottom of the probe and the bottom of the vessel as shown
in Example 2.
Example 2:
Level Units = inches
Level Units = Centimeters
Probe Model = 7zT
Probe Model = 7YT
Probe Mount = NPT
Probe Mount = NPT
Probe Length = 72 in
Probe Length = 90 cm
Level Offset = 10 in
Level Offset = 0 cm
When the ECLIPSE transmitter is mounted in a
Dielectric Range =
chamber/bridle, it is usually desirable to configure the unit
Dielectric Range = Above 10
Above 10
with the 4 mA Set Point (LRV) at the lower process con-
4 mA = 24 in
4 mA = 24 cm
nection and the 20 mA Set Point (URV) at the upper
process connection. The measuring range then becomes the
20 mA = 60 in
20 mA = 60 cm
center-to-center dimension. In this case, a negative Level
Offset needs to be entered. In doing so, all measurements
are then referenced at a point up on the probe, as shown in
Example 3.
Application calls for a 90-cm Model 7zT coaxial probe
with an NPT process connection. The process medium is
water with the bottom of the probe 10 inches above the
bottom of the tank.
The user wants the 4 mA Set Point (LRV) at 24 cm and
the 20 mA Set Point (URV) at 60 cm as referenced from
the bottom of the probe.
Application calls for a 90-cm Model 7zT coaxial probe
with an NPT process connection. The process medium is
water with the bottom of the probe 10 inches above the
bottom of the tank.
The user wants the 4 mA Set Point (LRV) at 24 cm and
the 20 mA Set Point (URV) at 60 cm as referenced from
the bottom of the tank.