IP Server Connection Type

Figure 8: PW-7000 Host Port Configuration Screen with IP Server Connection
Step 1.
Note: In the previous panels, this selection was made manually by setting the DIP switches.
Step 2.
PW-7000 (PW7K1IC) Installation and Configuration Guide, Document 800-25673V1
From PW7000 Communication Address drop-down list, select one of the
eight (0 to 7) available communication addresses for the PW-7000
board.
For the Primary Host Port, make the following selections:
Connection Type. Select IP Server (the standard connection type), so that the
Pro-Watch Host will poll the PW-7000 panel. The panel does not currently
support the IP Client option, which would cause the PW-7000 panel to poll the
Pro-Watch Host and the Host to reply to the panel.
Data Security. Select one of the following:
None
Password/AES from the drop-down list. If you select Password/AES,
communications between the Pro-Watch Host and the PW-7000 panel are
encrypted. Note that encryption must be enabled in Pro-Watch for the
appropriate Pro-Watch channel. See Chapter 7, "Hardware Configuration,"
in the Pro-Watch Guide for channel encryption instructions.
TLS Required
TLS if Available
Port Number. Enter the port number through which the host computer can
communicate with the PW-7000 board.