Figure 3-6: Mcs Tb1 Alarm Connections - Tyco Galaxy SC Controller Manual

Galaxy sc controller
Table of Contents

Advertisement

Remove TB1
Alarm Wiring
Issue 13 February 2001
Tyco Electronics Galaxy SC Controller J85501F-1
Repeat this procedure for each additional rectifier. When complete,
verify the plant charge bus is within tolerance and make final
adjustments if necessary.
Warning: Verify that only one wire is terminated on TB2 pins 1 and 2
on the controller. If other wires exist, determine what the leads are
feeding and their function. They may have to be jumpered around before
removing from TB2 or loss of loads may occur. Plants equipped with
ED83018-31GRP 17 low voltage disconnect panels are at risk.
1. Remove, mark or tag and insulate all external wires (office alarms)
terminated on TB1. See Figure 3-6.
2. Use Table 3-I to record wire colors.
Note: Galaxy Controller alarm connections do not require crimped
connections. If desired, cut the existing MCS alarm connections.
Leave adequate length for re-termination to the Galaxy Controller.
From
1
UPF
Office
UPF
Alarm
2
UPFR
Circuit
3
Input for
EQ
External
EQ
4
Boost
EQR
Control
5
SI(A)
BD
6
SI(A)
7
SI(B)
HV
8
SI(B)
9
SI(C)
RFA
10
SI(C)
From
Office
11
SI(D)
Alarm
LV2
Circuit
12
SI(D)
13
SI(E)
MJF
14
SI(E)
15
SI(F)
16
SI(F)
17
SI(G)
18
SI(G)
19
FAN
FAN
Alarm
20
FAJ
Inputs
FAJ

Figure 3-6: MCS TB1 Alarm Connections

ABSO
ABS1
ABS2
From
ABS3
Office
Alarm
FG
Circuit
A
D
BD
TR1
MNF
TR2
From
Engine
TR3
Control
Circuit
TR4
PMN
PMNR
PMNV
ANY
From
MINOR
PMNV
Office
Alarm
PMJ
Circuit
ANY
MAJOR
PMJR
PMJV
PMJR
X Normally Open-Closed on Alarm
– Normally Closed- Open on Alarm
21
F21
23
25
27
22
24
PMN
26
PMJ
28
BD
29
G1, 2, 9, 10
30
G3, 4, 11, 12
31
G5, 6, 13, 14
32
G7, 8, 15, 16
33
34
35
36
37
38
39
40
Installation 3 - 29