Specifications
Input (per module)
Typical
Breaker (customer provided)
Output (per module)
Output Voltage
10
Output Current
Output VA
Total Harmonic Distortion
(THD)
Regulation
Environmental
Temperature
Mechanical
Weight
Cooling
10
Not adjustable, at No-load
11
Regulation = (No-load voltage - Full-load voltage) / Full-load voltage.
12
Heat Release - per inverter, full load, typical. Special room cooling may be required.
Page 37
© Copyright 2021 ABB. All rights reserved.
SI5A120PME series
+24 Vdc Input
+21.0 to +32.0 Vdc
24.5 Vdc minimum
+27.0 Vdc
35.0 A maximum
668 W maximum
40 A minimum, per installed
module
5 A
maximum
ac
600 VA maximum
2 % maximum
314 BTU/hr
6.5 lb
Front to rear forced air
Table 9 Specifications - Inverter
SI10A120PME series
−48 Vdc Input
-42.5 to −60.0 Vdc
49.6 Vdc minimum
−54.0 Vdc
35.0 A maximum
1337 W maximum
40 A minimum, per installed
module
10 A
maximum
ac
778 BTU/hr
SI5A240PME series
−48 Vdc Input
-42.5 to −60.0 Vdc
−49.6 Vdc minimum
−54.0 Vdc
35.0 A maximum
1337 W maximum
40 A minimum, per installed
module
5 A
maximum
ac
1200 VA maximum
778 BTU/hr