Table 6 Alarm Outputs - ABB 827E Product Manual

Modular inverter system −48 v / +24 v input 120 vac / 240 vac output
Table of Contents

Advertisement

Alarm output cabling is available as an option. Order Part Number 6370213P-X, where X is the length
of the cable; see the J-drawing.
Note: In accordance with safety agency approval of this product, when connecting the plant alarm
interface, do not exceed NEC CLASS II for connections.
Terminal Type
DB25 female (gold)
5
Pin
Type
Description
13
MAJ
NC (K1, relay 1)
25
MAJ
COM (K1, relay 1)
12
MAJ
NO (K1, relay 1)
23
MAJ
NC (K1, relay 2)
11
MAJ
COM (K1, relay 2)
24
MAJ
NO (K1, relay 2)
10
MIN
NC (K2, relay 1)
22
MIN
COM (K2, relay 1)
9
MIN
NO (K2, relay 1
20
MIN
NC (K2, relay 2)
8
MIN
COM (K2, relay 2)
21
MIN
NO (K2, relay 2)
17
Plant Load
NC (K3, relay 1)
5
Plant Load
COM (K3, relay 1)
18
Plant Load
NO (K3, relay 1
7
Plant Load
NC (K3, relay 2)
19
Plant Load
COM (K3, relay 2)
6
Plant Load
NO (K3, relay 2)
14
K4B spare
NC (K3, relay 1)
2
K4B spare
COM (K3, relay 1)
15
K4B spare
NO (K3, relay 1
4
K4C spare
NC (K4, relay 2)
16
K4C spare
COM (K4, relay 2)
3
K4C spare
NO (K4, relay 2)
Note: MAJ alarm relay (K1) coil is DE-ENERGIZED on alarm. All other alarm relay coils are ENERGIZED
on alarm. Therefore, when the controller is unpowered, MAJ is asserted and all other alarms
are not asserted.
5
MAJ = Plant Major, MIN = Plant Minor
6
Alarm Cables J438827E L25 – L32
7
When combining signals of multiple shelf systems, wire Open on Alarm signals in series and Close on Alarm signals in parallel.
Page 25
© Copyright 2021 ABB. All rights reserved.
6
Black/Orange
Orange/Black
Black/Blue
Slate/Red
Red/Slate
Blue/Black
Red/Brown
Brown/Red
Red/Green
Orange/Red
Red/Orange
Green/Red
Brown/White
White/Brown
Slate/White
Red/Blue
Blue/Red
White/Slate
Blue/White
White/Blue
Orange/White
White/Green
Green/White
White/Orange

Table 6 Alarm Outputs

Recommended Wire Size
22 GA
Connection to Combine
Function
Close on Alarm
Common K1-1
Open on Alarm
Close on Alarm
Common K1-2
Open on Alarm
Open on Alarm
Common K2-1
Close on Alarm
Open on Alarm
Common K2-2
Close on Alarm
Open on Alarm
Common K3-1
Closed on Alarm
Open on Alarm
Common K3-2
Closed on Alarm
Open on Alarm
Common K4-1
Closed on Alarm
Open on Alarm
Common K4-2
Closed on Alarm
7
Signals
Parallel
Series
Parallel
Series
Series
Parallel
Series
Parallel
Series
Parallel
Series
Parallel
Series
Parallel
Series
Parallel