Table 10 Specifications - Inverter System - ABB 827E Product Manual

Modular inverter system −48 v / +24 v input 120 vac / 240 vac output
Table of Contents

Advertisement

AC Configuration
Configuration
Mechanical
Height (shelf)
Depth (shelf)
Width (shelf)
Mounting
Inputs/Outputs
Input Voltage and Current
Output Voltage
Output kVA per shelf
Alarm Contact Ratings
Shelf Distribution Disconnect Module Output Protection
Circuit Breaker
Environmental
Acoustic Noise
Temperature
Ambient
Operating
Storage
Humidity
Shock
Vibration
Installation Area
Installation Area Limitations
Safety and Standards
Safety
NEBS
Electromagnetic Immunity
Radiated and Conducted
Emissions
Radiated Emissions
Electrostatic Discharge
Page 38
© Copyright 2021 ABB. All rights reserved.
Line to Neutral, Single Phase
8.72"
15.03"
Available for 19" or 23" Rack Mounting
Relay Rack or Cabinet
per installed Inverters - See Table 9 Specifications - Inverter
per installed Inverters - See Table 9 Specifications - Inverter
−48 Vdc
23"
7.2 kVA
+24 Vdc
23"
3.6 kVA
60 Vdc at 0.5A
100A single pole
45 dBA at 3 meters
Sea Level to 4800 feet
0 to +45 °C continuous
-40 to +85 °C
<95% Non-condensing
This equipment, in its shipping container, withstands shock developed
without physical damage or degradation of the electrical performance.
This equipment, in its shipping container, withstands vibration encountered in shipping
without physical damage or degradation of the electrical performance.
Install only in restricted access areas (dedicated equipment rooms, equipment closets,
or the like) in accordance with articles 110-26, 110- 27, and 110-18 of the U.S. National
Electric Code (NEC-2011), ANSI/NFPA No. 70, and pursuant to applicable local codes.
ETL Listed
NEBS Level 3 Tested and Complaint
Meets Telcordia GR-1089-CORE ISSUE 6 [IEC801-2 level 2,4,5
FCC Class A, EN55022 (CISPR22) level A
EN61000-4-2 Level 1-4

Table 10 Specifications - Inverter System

19"
4.8 kVA
19"
2.4 kVA
shipping