Table 4 Typical Trip Ratings For 10 - 30 Amp Ac Circuit Breakers - ABB 827E Product Manual

Modular inverter system −48 v / +24 v input 120 vac / 240 vac output
Table of Contents

Advertisement

NOTE: The LINE and NEUTRAL of all shelves in a multiple-shelf system must be connected together
in an AC distribution panel or optional maintenance bypass panel (refer to J-Drawing 438827E
List number 51 and 52).
NOTE: The inverter's output protection will shutdown the inverter output after 5 seconds under
short circuit or deep overload conditions. Therefore, the response time of the breaker must
allow the breaker to trip within (4) seconds with a short circuit current of 28A per inverter.
Both the circuit breaker rating and number of inverters equipped in the system must be taken
into account to insure that the circuit breaker trips in the desired timeframe. If faster
response times are desired, e.g. below the AC holdup time of the AC equipment, then the trip
time must be decreased by lowering trip rating of the breaker, and/or increasing the number
of modules equipping the system.
Table 4 shows typical trip times of commercially available AC distribution circuit breakers. The table
lists "min-max" trip times based on most common circuit breaker ratings vs. number of equipped
−48 V inverters in the system. The maximum rating must be used to guarantee tripping within a
specific time. For special situations where commercial AC breakers do not meet the required trip
times, contact technical support for other options.
Number
Avail.
10 A Trip Time
of −48 V
Trip
(msec.)
Inverters
Current
(A)
Min
3
84
400
4
112
5
5
140
5
6
168
5
7
196
5
8
224
5
9
252
5
10
280
5
11
308
5
12
336
5
13
364
5
14
392
5
15
420
5
16
448
5
17
476
5
18
504
5
19
532
5
20
560
5
21
588
5
22
616
5
23
644
5
24
672
5
* Circuit breaker rating not recommended for this number of inverters equipped
Page 22
© Copyright 2021 ABB. All rights reserved.
15 A Trip Time
(msec.)
Max
Min
Max
2000
700
3000
1300
5
1600
800
5
1100
700
5
800
450
5
600
300
5
300
18
5
20.00
17.5
5
18.00
15
5
17.00
16.67
5
16.67
16.67
5
16.67
16.67
5
16.67
16.67
5
16.67
16.67
5
16.67
16.67
5
16.67
16.67
5
16.67
16.67
5
16.67
16.67
5
16.67
16.67
5
16.67
16.67
5
16.67
16.67
5
16.67
16.67
5
16.67
Table 4 Typical Trip Ratings for 10 – 30 Amp AC Circuit Breakers
20 A Trip Time
25 A Trip Time
(msec.)
(msec.)
Min
Max
Min
1250*
5000*
1700*
400
2800
900
5
1600
600
5
900
400
5
600
250
5
400
60
5
18
5
5
17
5
5
16.67
5
5
16.67
5
5
16.67
5
5
16.67
5
5
16.67
5
5
16.67
5
5
16.67
5
5
16.67
5
5
16.67
5
5
16.67
5
5
16.67
5
5
16.67
5
5
16.67
5
5
16.67
5
30 A Trip Time
(msec.)
Max
Max
7000*
4500*
20000*
3700
2250*
9000*
2500
1300*
5500*
1800
1000
4000
1300
600
2800
1000
475
2250
850
300
1700
700
200
1300
600
5
1200
500
5
1000
450
5
800
425
5
700
375
5
600
350
5
550
300
5
500
275
5
450
250
5
400
225
5
375
215
5
350
200
5
325
175
5
300
150
5
275