Distribution Monitor (Dm); System Controller - ABB 827E Product Manual

Modular inverter system −48 v / +24 v input 120 vac / 240 vac output
Table of Contents

Advertisement

Distribution Monitor (DM)

The Distribution Monitor
current. In addition
Indicators on Distribution Monitor: OK LED (green) reports plant status.
Note: This LED will not be illuminated if the distribution monitor has an internal fault or if CB1 is
open.

System Controller

The System Controller
and inverter setpoints either from the front panel or through the serial interface located on the front
panel. A modem is optional for remote access; refer to the J-Drawing L20 and L22 for modem and
software ordering information. The System Controller is easy to use, convenient, and allows the user
to quickly change system setpoints without accessing the inside of the inverters.
Indicators on System Controller:
Controller LED (green) indicates that the Distribution Module has passed its internal self- test.
Inverter Minor LED (amber) is a summation alarm indicator and reports plant status in a variety
of ways, depending on the condition. The reported conditions are defined in the condition chart
provided in the Troubleshooting section.
Inverter Major LED (red) is a summation alarm indicator and reports plant status in a variety of
ways, depending on the condition. The reported conditions are defined in the condition chart
provided in the Troubleshooting section.
Adjustable Alarm Setpoints: Setpoints are adjusted through the System Controller.
Refer to Adjusting Setpoints for more detail.
Alarm Settings Associated with Plant: Settings are for 120 V
V
and +24 V
plants are in parentheses.
ac
dc
Plant Low Voltage Alarm Setpoint
Range 90.0 to 120.0 V
Factory set to 95 V
Plant High Voltage Alarm Setpoint
Range 110.0 to 140.0 V
Factory set to 130 V
Battery Low Voltage Alarm Setpoint (for –48 Vdc input inverter system)
Range -42.0 to -55.0V
Factory set to -44.0V
Number of Redundant Inverters Setpoint
Range 0 to 5.
Factory set to 1.
Percent of Capacity Setpoint
Adjustable from 0% to 100% in steps of 10.
Factory set to 80%.
Page 41
© Copyright 2021 ABB. All rights reserved.
13
(Figure 2) provides the system monitoring including AC voltage, and AC
13
(Refer to Figure 2) allows the user to view plant status and change system
(180.0 to 240 V
ac
(190 V
)
ac
ac
(220.0 to 280 V
ac
(260 V
)
ac
ac
(21.0 to 27.5V
dc
(22.0V
)
dc
dc
and 48 V
ac
)
ac
)
ac
)
dc
plants. Settings for 240
dc