2.3.3 - Milliampere Input

A current source of 4 to 20 mA can be applied to terminals 1(+) and 3(-) for
input 1 and to terminals 4(+) and 6(-) for input 2. The current signal can be generated
by a transmitter with an external power supply. In case of using the 24 VDC internal
voltage source from the Indicator to power a two-wire transmitter, the current is
received only by terminal 1(+) for input 1 and by terminal 4(+) for input 2. Figure 8
shows both possibilities of connection.
Figure 8 - Milliampere Input
Installation