Mitsubishi Heavy Industries SCM71ZM-S1 Technical Manual page 305

Inverter multi-split system residential air-conditioners
Table of Contents

Advertisement

 
2 . Accessories & Prepare on site
Following parts are provided.
Accessories
R/C main unit, wood screw (ø3.5 x 16) 2 pcs, Quick reference
Following parts are arranged at site. Prepare them according to the respective installation procedures.
Item name
Switch box
For 1 piece or 2 pieces (JIS C 8340 or equivalent)
Thin wall steel pipe for electric
appliance directly on a wall.
(JIS C 8305 or equivalent)
Lock nut, bushing (JIS C 8330 or equivalent)
Lacing (JIS C 8425 or equivalent)
Putty
Molly anchor
R/C cable (0.3 mm
2
x 2 pcs)
 
3 . Installation place
Secure the installation space shown in the figure.
For the installation method, "embedding wiring" or "exposing wiring"
can be selected.
For the wiring direction, "Backward", "Upper center" or "Upper left"
can be selected.
Determine the installation place in consideration of the installation
method and wiring direction.
Q'ty
Remark
1
These are not required when installing
As required
directly on a wall.
As required
As required
Necessary to run R/C cable on the wall.
Suitably
For sealing gaps
As required
As required
See right table when longer than 100 m
Installation space
30mm
30mm
304
-
-
When the cable length is longer than 100 m,
the max size for wires used in the R/C case
2
is 0.5 mm
. Connect them to wires of larger
size near the outside of R/C. When wires are
connected, take measures to prevent water,
etc. from entering inside.
≦ 200 m
≦ 300m
≦ 400m
≦ 600m
30mm
30mm
Wiring
配線
30mm
30mm
R/C temperature sensor
Secure minimum spaces for disassembling the case.
Upper left and Upper right sides
......30mm or more
Bottom side...120mm or more
If using L-shaped screw driver, 50mm or more is
available.
'17 • SCM-T-225
2
0.5 mm
x 2 cores
2
0.75 mm
x 2 cores
2
1.25 mm
x 2 cores
2
2.0 mm
x 2 cores