Scope of performance of the CPs
The CPs support the following SNMP version:
● CP 1542SP-1
– SNMPv1
● CP 1543SP-1, CP 1542SP-1 IRC
– SNMPv1
– SNMPv3 (with activated Security functions)
For information on configuring SNMPv3, see section SNMP (Page 73).
Traps are not supported by the CP.
Supported MIBs in SNMPv1
The CPs support the following MIBs:
● MIB II (acc. to RFC1213)
The CP supports the following groups of MIB objects:
– System
– Interfaces
– IP
– ICMP
– TCP
– UDP
– SNMP
● LLDP MIB
CP 154xSP-1
Operating Instructions, 12/2019, C79000-G8976-C426-05
Diagnostics and maintenance
6.3 Diagnostics with SNMP
91