Configuration
4.1 Security recommendations
Table 4- 1
Server ports (all three CP types)
Protocol / function
Port number (pro-
tocol)
DHCP
68 (UDP)
S7 and online con-
102 (TCP)
nections
HTTP
80 (TCP)
HTTPS
443 (TCP)
SNMP
161 (UDP)
* Some service providers consider the opening of port 102 a security vulnerability.
To avoid opening the port during online diagnostics, see section Online security diagnostics
via port 8448 (CP 1542SP-1 IRC, CP 1543SP-1) (Page 90).
Table 4- 2
Server ports - only CP 1542SP-1 IRC and CP 1543SP-1
Protocol / function
Port number (pro-
tocol)
Online diagnostics
102 (TCP)
Communication via
443 (TCP)
SINEMA RC
Syslog
514 (UDP)
Table 4- 3
Server ports - only CP 1542SP-1 IRC
Protocol / function
Port number (pro-
tocol)
DNP3
20000 (TCP/UDP)
can be set
IEC 60870-5-104
2404 (TCP)
can be set
52
Default of the
Port status
port
Closed
Open after configuration (while the
CP obtains a new address)
Closed
Open after configuration *
Closed
Open after configuration
Closed
Open after configuration
Open
Open after configuration
Default of the
Port status
port
Closed
Open after configuration
Closed
Open after configuration
Closed
Open after configuration
Default of the
Port status
port
Closed
Open after configuration
Closed
Open after configuration
Operating Instructions, 12/2019, C79000-G8976-C426-05
Authentication
No
No
Yes
Yes
Yes (with SNMPv3)
Authentication
No
Yes
No
Authentication
Yes, when Secure
Authentication is ena-
bled.
No