Table 9.12 Electrical data, 60Hz water/glycol-cooled systems using single-point power kit,
evaporator with belt-drive blowers and indoor condensing unit (continued)
Base Evaporator
Model Number
Condensing Unit
Model Number
with Humidifier
FLA
WSA
OPD
with Electric Reheat and Humidifier
FLA
WSA
OPD
with SCR Reheat and Humidifier
FLA
WSA
OPD
* Specify disconnect or no disconnect
Notes:
1.
Belt drive data includes externally mounted high static blower box, powered from evaporator unit.
2.
Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
3.
SCR Reheat not available with MM*24K or MM*36K.
Table 9.13 Electrical data, 50Hz water/glycol-cooled
systems using single-point power kit, evaporator with
direct-drive blowers and indoor condensing unit
Base Evaporator Model Number
Condensing Unit Model Number
Cooling Only
FLA
with Electric Reheat
FLA
2
with SCR Reheat
FLA
with Humidifier
Vertiv | Liebert Mini-Mate2—2 and 3 ton Technical Data Manual |
208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
MM*24E
MM*36E
MM*24E
MC*26W
MC*38W
MC*26W
27.6
32.7
22.5
30.6
37.0
25.1
40
50
35
46.2
51.3
38.5
55.5
61.8
46.5
60
70
50
3
56.8
74.4
47.8
67.1
89.1
56.7
70
90
60
220 - 1 Ph - 50Hz
MM*35E
MC*37W
19.9
7.8
44.9
17.5
61.6
21.7
208/230 - 3 Ph - 60Hz
MM*36E
MM*24E
MM*36E
MC*38W
MC*26W
MC*38W
26.4
—
23.2
30.0
—
26.2
40
—
35
42.4
—
33.6
51.4
—
40.8
60
—
45
62.5
—
47.3
75.1
—
56.3
80
—
60
380/415 - 3 Ph - 50Hz
MM*35E
MC*37W
460 - 3 Ph - 60Hz
MM*24E
MM*36E
MC*26W
MC*38W
—
11.9
—
13.5
—
15
—
16.9
—
20.6
—
20
—
24.0
—
28.6
—
30
56
Need help?
Do you have a question about the Liebert Mini-Mate2 MMD24E and is the answer not in the manual?