Table 7.2 Water/glycol data, 50Hz
Evaporator Model
Condensing Unit Fluid
DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM
80°F DB, 62.8°F WB (26.7°C DB,
17.1°C WB) 38%RH
75°F DB, 61°F WB (23.9°C DB,
16.1°C WB) 45%RH
72°F DB, 60°F WB (22.2°C DB,
15.5°C WB) 50%RH
Fan Data - Evaporator
CFM (CMH), High Speed
CFM (CMH), Low Speed
Fan Motor HP (W)
External Static Pressure, in (mm) water gauge
Evaporator Coil - Copper Tube/Aluminum Fin
2
2
Face Area, ft
(m
)
Coil Rows
Max Face Velocity, fpm (m/s)
Unit Refrigerant Charge, oz. (kg)
Unit Operating Weight, lb (kg)
Electric Reheat Capacity (Includes Fan Motor)-kW (Btuh)
Input Voltage 220-1-50
Input Voltage 380-3-50
SCR Reheat Capacity (Includes Fan Motor)-kW (Btuh)
Input Voltage 220-1-50
Input Voltage 380-3-50
Humidifier Data - Steam Generator Type
Steam capacity - lbs/hr (kg/hr)
Electrical Input Power, kW
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip Coupling Size
Suction Line Diameter - Aeroquip Coupling Size
Humidifier Supply
Evaporator/Condensate Drain
MERV 8 Filter, External Filter Box, qty (1), Nom. Size, in. (mm)
MERV 8 Filter, Air Distribution Plenum, qty (1), Nom. Size, in. (mm)
Condensing Unit Model Number
Condenser Fluid Requirements
THR - kW (Btuh) @ 75F/45%RH
Vertiv | Liebert Mini-Mate2—2 and 3 ton Technical Data Manual |
Total
Sensible
Total
Sensible
Total
Sensible
MMD35E or MMD35K
Water-Cooled
11.3 (38,700)
10.1 (34,400)
11.0 (37,400)
9.00 (30,700)
10.7 (36,600)
8.30 (28,400)
1250 (2124)
)
1000 (1699
0.5 (0.38)
0.3 (8)
3.1 (0.29)
3
394 (2.0)
7 (0.20)
225 (102)
5.3 (18090)
7.3 (24900)
8.7 (29700)
10.3 (35100)
4.3 (2.0)
1.5
3/8" - #6 Female
7/8" - #11 Female
1/4" OD Copper Compression Fitting
3/4" NPT-Female
4x20x20 (102x508x508)
4x16x25 (102x406x635)
MCD37W
85°F (29.4°C) EWT
14.0 (47,800)
Glycol-Cooled
9.20 (31,400)
9.00 (30,700)
8.80 (30,100)
8.00 (27,300)
8.60 (29,400)
7.35 (25,100)
110°F (43.3°C) EGT - 40% PG
13.2 (44,900)
31
Need help?
Do you have a question about the Liebert Mini-Mate2 MMD24E and is the answer not in the manual?