9 ELECTRICAL DATA
Table 9.1 Direct drive split system evaporator or chilled water unit electrical data, 60Hz
Base Evaporator Model
Number
Cooling Only
FLA
WSA
OPD
with Electric Reheat
FLA
WSA
OPD
4
with SCR Reheat
FLA
WSA
OPD
with Humidifier
FLA
WSA
OPD
with Electric Reheat and Humidifier
FLA
WSA
OPD
4
with SCR Reheat
and Humidifier
FLA
WSA
OPD
* Specify disconnect or no disconnect
Notes:
1.
Use MM*36E electrical data for MM*40C chilled water units
2.
For units with Hot Water Reheat (available only on MM*40C units), use appropriate values from "Cooling only" or "with Humidifier"
categories.
3.
Use MM*24E and MM*36E for MM*24K & MM*36K, respectively, except with SCR reheat.
4.
SCR Reheat not available with MM*24K, MM*36K or MM*40C.
Vertiv | Liebert Mini-Mate2—2 and 3 ton Technical Data Manual |
208/230 - 1 Ph - 60Hz
277 - 1 Ph - 60Hz
MM*24E
MM*36E
MM*24E
2.8
2.8
2.3
3.5
3.5
2.9
15
15
15
27.8
27.8
24.0
34.8
34.8
30.0
35
35
35
32.0
44.5
27.6
40.0
55.6
34.5
45
60
35
9.2
9.2
8.0
11.5
11.5
10.0
15
15
15
34.2
34.2
29.7
42.8
42.8
37.1
45
45
40
38.4
50.9
33.3
48.0
63.6
41.6
50
70
45
208/230 - 3 Ph - 60Hz
MM*36E
MM*24E
MM*36E
2.3
—
2.8
2.9
—
3.5
15
—
15
24.0
—
19.6
30.0
—
24.5
35
—
25
38.4
—
26.9
48.0
—
33.6
50
—
35
8.0
—
9.2
10.0
—
11.5
15
—
15
29.7
—
26.0
37.1
—
32.5
40
—
35
44.1
—
33.3
55.1
—
41.6
60
—
45
460 - 3 Ph - 60Hz
MM*24E
MM*36E
—
1.4
—
1.8
—
15
—
9.8
—
12.3
—
15
—
13.5
—
16.9
—
20
—
4.8
—
6.0
—
15
—
13.2
—
16.5
—
20
—
16.9
—
21.1
—
25
45
Need help?