Description
Data transmission order
Communication function
(Note 1)
Baud rate, transmission format, and applications of communication should be set using the tool
software.
(Note 2)
When communication is performed at a baud rate of 38,400 bit/s or higher, the cable length should be
within 3 m. For wiring the RS-232C, a shielded wire must be used to increase noise suppression.
(Note 3)
When connecting a commercially available device, please confirm operation using the actual device.
(Note 4)
Each SD, RD and SG terminal of the RS-232C port is insulated from the internal circuit.
■
LAN port (CPS4RE/CPS3RE)
Description
Interface
Baud rate
Cable total length
Communication cable
No. of nodes
Number of simultaneous
connections
Communication protocol
(Communication layer)
DNS
DHCP/DHCPV6
FTP server/Client
(Supports SSL)
HTTP server/Client
(Supports SSL)
SMTP client (Supports
SSL)
SNTP
General-purpose
communication
Dedicated communication
(Note 1)
Switching between different speeds is done automatically by auto negotiation function.
(Note 2)
System connection is used when connecting tool software via LAN.
WUME-FP7CPUH-09
Parity: No / Yes (Odd / Even)
Start code: Without STX / With STX
End code: CR / CR + LF / None / ETX
Stop bit: 1 bit / 2 bits
Transmits from bit 0 character by character.
MEWTOCOL-COM (master/slave), MEWTOCOL7-COM (slave) MODBUS RTU
(master/slave) general-purpose communication modem initialization
100BASE-TX / 10BASE-T
100 Mbps/10 Mbps automatic negotiation
100 m (500 m when using a repeater)
UTP (Category 5)
254 unit
Max. 220 (User connections: 216, System connections 4)
TCP/IP, UDP/IP
Supports name server
Automatic getting of IP address
Server function File tranmission, No. of users: 3
Client function Data and file transmission
Server function System WEb, Customer WEB (8 MB), No. of simultaneous
sessions: 16
Client function Data transmission
Client function Mail transmission
Time synch function
16 kB/connection (User connections 1 to 16)
Slave
MEWTOCOL-COM, MEWTOCOL7-COM, MEWTOCOL-DAT,
communication
MODBUS-TCP, MC protocol
Master
MEWTOCOL-COM, MEWTOCOL-DAT, MODBUS-TCP, MC
communication
protocol
8.1 CPU Unit Specifications
Rated voltage
Rated voltage
(Note 1)
8-7