Appendix 1 Specifications - KStar YMK3300-200k Operation Manual

Table of Contents

Advertisement

Model
Cabinet capacity (VA/W)
Module capacity (VA/W)
Max. module number
Rated Voltage
Voltage Range
Input
Frequency Range
Power Factor
Current THDi
Bypass Voltage
Rated Voltage
Power Factor
Voltage Regulation
Frequency
Crest Factor
Output
Battery

Appendix 1 Specifications

Phase
138~485Vac
◆ At 40°C: The UPS works at full load when the voltage is
323–485Vac and is derated load when the
voltage is 323–138Vac
◆ At 30°C: The UPS works at full load when the voltage is
305–485Vac and is derated load when the
voltage is 305–138Vac
Max.voltage: 220V:+25 %( optional +10%, +15%, +20%);
Range
Min. voltage:-45 %( optional -10%, -20%,-30%)
Frequency protection range: ±10%
Phase
Utility
±1%/±2%/±4%/±5%/±10%of the rated frequency(optional)
Mode
Battery
Mode
THD
Inverter overload capability:
◆ 105% < load ≤ 110%: transfer to bypass mode after 60
min
◆ 110% < load ≤ 125%: transfer to bypass mode after 10
min
Overload
◆ 125% < load ≤ 150%: transfer to bypass mode after 1
min
Bypass overload capability:
◆ Temperature ≤ 30°C, load ≤ 135%: run for a long time
◆ Temperature ≤ 40°C, load ≤ 125%: run for a long time
◆ 1000% load: run for 100 ms
Optional Voltage:
±180V/192V/±204V/±216V/±228V/±240/±252/±264/±276/±
288/±300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs
Voltage
optional)
360Vdc~600Vdc (30~40 pcs, 36 pcs define, 36 and 50 pcs
no power derating; 32~34 pcs output power factor 0.9;30
pcs output power factor 0.8;)
150kVA
50k~150k /
50k~250k /
50k~150k
3
3 Phase 4 Wires and Ground
380/400/415Vac
40Hz-70Hz
≤3%(100% nonlinear load)
230V:+20 %( optional +10%, +15%);
240V:+15 %( optional +10%);
3 Phase 4 Wires and Ground
380/400/415Vac
(50/60±0.1)Hz
≤2% with linear load
≤4% with non linear load
68
250kVA
50k~200k /
50k~250k
50k / 50k
5
≥0.99
1
±1%
3:1
200kVA
50k~200k
4